电缆燃烧试验新旧标准的火灾动力学仿真对比分析
引用本文:高俊国,孔译辉,孙伟峰,李明,房权生,张晓虹.电缆燃烧试验新旧标准的火灾动力学仿真对比分析[J].中国安全生产科学技术,2018,14(8):165-170.
作者姓名:高俊国  孔译辉  孙伟峰  李明  房权生  张晓虹
作者单位:(1. 哈尔滨理工大学 工程电介质及其应用教育部重点实验室,黑龙江 哈尔滨 150080;2.宝胜集团有限公司,江苏 扬州 225800)
摘    要:为了研究国家标准的变化对成束电缆燃烧试验的影响,使用FDS软件进行电缆燃烧性能的火灾动力学模拟研究。对新旧国家标准进行燃烧模拟,比较分析箱体温度、热释放速率(HRR)、电缆前后表面温度和烟密度仿真结果,考察新旧国家标准间的差异因素对燃烧的动力学过程的影响,根据模拟结果探讨新国家标准下电缆通过燃烧试验的难易程度和电缆的优化设计。研究结果表明:新标准对炭化高度要求更严格,故在保证电缆机械强度的前提下,为达到新标准中的B1级阻燃等级,应在旧标准A类阻燃的基础上增加电缆的阻燃效果,特别需要抑制火焰在电缆表面垂直蔓延的能力。

关 键 词:电缆  燃烧性能  国家标准修订  动力学仿真

Comparative analysis of fire dynamics simulation on new and old standards of cable combustion tests
GAO Junguo,,KONG Yihui,SUN Weifeng,LI Ming,FANG Quansheng,ZHANG Xiaohong.Comparative analysis of fire dynamics simulation on new and old standards of cable combustion tests[J].Journal of Safety Science and Technology,2018,14(8):165-170.
Authors:GAO Junguo    KONG Yihui  SUN Weifeng  LI Ming  FANG Quansheng  ZHANG Xiaohong
Affiliation:(1. Key Laboratory of Engineering Dielectrics and Its Application of Ministry of Education, Harbin University of Science and Technology, Harbin Heilongjiang 150080, China;2. Baosheng Group Co., Ltd., Yangzhou Jiangsu 225800, China)
Abstract:In order to study the influence of the change of national standard on the combustion tests of bunched cables, the fire dynamics simulation on the combustion performance of cable was carried out by using FDS software. The combustion simulation was conducted on the new and old national standards, and the simulation results of the chamber temperature, heat release rate (HRR), front and rear surface temperature of cable and smoke density were compared and analyzed. The influence of different factors between the new and old national standards on the dynamic process of combustion was investigated, and the difficulty degree of the cable passing the combustion tests and the optimization design of cable under the new national standard were discussed according to the simulation results. It showed that the requirement of the carbonization height in the new standard was more strict, so on the premise of guaranteeing the mechanical strength of cable, in order to achieve the B1 class flame retardant grade in the new standard, the flame retardant effect of cable should be increased on the basis of A class flame retardant grade in the old standard, and the ability to restrain the vertical spread of flame on the surface of cable was required especially.
Keywords:cable  combustion performance  national standard revision  dynamics simulation
本文献已被 CNKI 等数据库收录!
点击此处可从《中国安全生产科学技术》浏览原始摘要信息
点击此处可从《中国安全生产科学技术》下载全文