Most industrial powder processes handle mixtures of various flammable powders. Consequently, hazard evaluation leads to a reduction of the disaster damage that arises from dust explosions. Determining the minimum ignition energy (MIE) of flammable mixtures is critical for identifying possibility of accidental hazard in industry. The aim of this work is to measure the critical ignition energy of different kinds of pure dusts with various particle sizes as well as mixtures thereof.The results show that even the addition of a modest amount of a highly flammable powder to a less combustible powder has a significant impact on the MIE. The MIE varies considerably when the fraction of the highly flammable powder exceeds 20%. For dust mixtures consisting of combustible dusts, the relationship between the ignition energy of the mixture and the minimum ignition energy of the components follows the so-called harmonic model based upon the volume fraction of the pure dusts in the mixture. This correlation provides results which show satisfactory agreement with the experimental values.  相似文献   

2.
In this study, the dependence of minimum ignition energies (MIE) on ignition geometry, ignition source radius and mixture composition is investigated numerically for methane/air and iso-octane/air mixtures. Methane and iso-octane are both important hydrocarbon fuels, but differ strongly with respect to their Lewis numbers. Lean iso-octane air mixtures have particularly large Lewis numbers. The results show that within the flammability limits, the MIE for both mixtures stays almost constant, and increases rapidly at the limits. The MIEs for both fuels are also similar within the flammability limits. Furthermore, the MIEs of iso-octane/air mixtures with a small spherical ignition source increase rapidly for lean mixtures. Here the Lewis number is above unity, and thus, the flame may quench because of flame curvature effects. The observations show a distinct difference between ignition and flame propagation for iso-octane. The minimum energy required for initiating a successful flame propagation can be considerably higher than that required for initiating an ignition in the ignition volume. For iso-octane with a small spherical ignition source, this effect was observed at all equivalence ratios. For iso-octane with cylindrical ignition sources, the phenomenon appeared at lower equivalence ratios only, where the mixture's Lewis number is large. For methane fuel, the effect was negligible. The results highlight the significance of molecular transport properties on the decision whether or not an ignitable mixture can evolve into a propagating flame.  相似文献   

3.
Quantifying the risk of accidental ignition of flammable mixtures is extremely important in industry and aviation safety. The concept of a minimum ignition energy (MIE), obtained using a capacitive spark discharge ignition source, has traditionally formed the basis for determining the hazard posed by fuels. While extensive tabulations of historical MIE data exist, there has been little work done on ignition of realistic industrial and aviation fuels, such as gasoline or kerosene. In the current work, spark ignition tests are performed in a gaseous kerosene–air mixture with a liquid fuel temperature of 60 °C and a fixed spark gap of 3.3 mm. The required ignition energy was examined, and a range of spark energies over which there is a probability of ignition is identified and compared with previous test results in Jet A (aviation kerosene). The kerosene results are also compared with ignition test results obtained in previous work for traditional hydrogen-based surrogate mixtures used in safety testing as well as two hexane–air mixtures. Additionally, the statistical nature of spark ignition is discussed.  相似文献   

4.
In order to prevent dust explosions due to electrostatic discharges (ESD), this paper reports the minimum ignition energy (MIE) of aluminum powders in the air and the effective nitrogen (N2) concentration for the inert technique. The Hartman vertical-tube apparatus and five kinds of different sized pure aluminum powders (median particle size, D50; 8.53 μm–51.2 μm) were used in this study. The statistic minimum ignition energy (MIEs) of the most sensitive aluminum powder used in this study was 5 mJ, which was affected by the powder particle size (D50; 8.53 μm). In the case of aluminum powder, the inerting effects of N2 were quite different from the polymer powders. The MIE of aluminum powder barely changed until the N2 concentration was 89% in comparison with that of the normal air. When the N2 concentration was 90%, the MIE of aluminum powders suddenly exceeded 1000 mJ, which does not occur easily with ESD in the industrial process.  相似文献   

5.
In general terms, the purpose of any safety standard is to define borderlines between safe and unsafe conditions, with reasonable safety margins. The electrical spark ignition sensitivity of dust clouds (MIE) varies over at least eight orders of magnitude. Therefore, in the case of intrinsically safe electrical apparatus to be used in the presence of explosive dust clouds, substantial differentiation of the minimum requirements to prevent ignition by electrical sparks is needed. The present paper proposes a method by which adequate differentiation of required maximum permissible currents and/or voltages in intrinsically safe electrical circuits to be used in explosive dust clouds can be achieved. In essence, the concept is to use conservative first-order ignition curves, calculated or estimated from the experimental MIE value of clouds in air of the actual dust. Charts to be used for design purposes are given in the paper. Internationally standardised test methods allow MIE for clouds of any dust to be determined, at least down to the range of a few mJ. There is, however, a need for a supplementary method covering the range of lower energies, down to 0.01 mJ.  相似文献   

6.
The original break spark test apparatus for intrinsically safe circuits was modified to allow the measurements of minimum ignition currents (MICs) at different initial pressures between 20 and 120 kPa. The MICs of different propylene/air mixtures at ambient temperature and at both atmospheric and sub-atmospheric pressures were measured. The corresponding minimum ignition energies (MIEs) using break sparks were calculated and compared with those derived from MIE/quenching distance correlations using high voltage sparks between flanged electrodes.  相似文献   

7.
The knowledge of the ignition behavior of dust–air mixtures due to electrical sparks (MIE, Minimum Ignition Energy) and hot surfaces (MIT, Minimum Ignition Temperature) is important for risk assessments in chemical production plants. The ignition behavior determines the extent and hence the cost of preventive protection measures.This paper describes the use of the minimum ignition energy and minimum ignition temperature as very important safety indexes in practice.  相似文献   

8.
This work aims to help improve the electrostatic safety design and explosion prevention of medical facilities. In this study, the minimum ignition energies (MIEs) of Florfenicol, Tilmicosin and mixtures of Florfenicol and Tilmicosin at ratios of 1:1, 1:2, 2:1 and 1:4 were measured in a Hartmann apparatus. The results demonstrated that the MIEs for Florfenicol, Tilmicosin and mixtures of Florfenicol and Tilmicosin at ratios of 1:1, 1:2, 2:1 and 1:4 are 200, 70, 180, 150, 200 and 110 mJ, respectively. Tilmicosin is more sensitive to static electricity, which is more dangerous than the other two powders examined in this paper. Furthermore, the MIEs of the mixtures are proportional to the Florfenicol content. For all powders, the MIE first decreased with the powder mass and later reached its minimum value. In addition, scanning electron microscopy (SEM), differential scanning calorimetry (DSC) were used to investigate the morphological specificity and thermal decomposition of the powders to elucidate the parameters governing the powder explosions further.  相似文献   

9.
6氨基青霉烷酸(6-APA)是生产阿莫西林的重要中间体,在生产过程的离心机分离及干燥等环节存在粉体燃烧爆炸的危险。利用Hartmann管式粉尘最小点火能测试装置,研究6-APA干粉状态及丙酮存在环境粉体最小点火能变化规律。实验结果表明,6-APA粉体在分散质量为0.6g时,最小点火能为14mJ,参照VDI2263的规定,属于一般着火敏感性粉尘。向粉体中加入丙酮溶剂模拟实际生产环境,实验结果显示粉尘云最小点火能下降明显,且混合物着火能力增强。质量为1g的6-APA粉体与0.5mL丙酮溶剂配比条件下,混合物分散质量为0.6g时,最小点火能为6mJ,在此环境中混合粉体属于特别着火敏感性粉尘。实验结果阐明了6-APA在丙酮存在环境条件下混合粉体燃烧的爆炸危险性,为采取相应的爆炸防护措施提供了实验依据。  相似文献   

10.
为研究超细聚苯乙烯微球粉体的燃爆特性,通过粉尘层最低着火温度测试装置、MIE-D1.2最小点火能测试装置、20 L球形爆炸测试装置,对其最低着火温度、最大爆炸压力、最小点火能量(MIE)等爆炸特性参数进行测定,探讨了加热温度、点火延滞时间、粉尘质量浓度、粉尘粒径对粉体燃爆特性的影响。结果表明:超细聚苯乙烯微球粉尘层在350℃左右时会发生无焰燃烧,且加热温度越高,粉体粒径越小,粉尘层发生着火时所需的时间越短;当粉体质量浓度为250 g/m3时,最大爆炸压力达到0.65 MPa,质量浓度为500 g/m3时,最大爆炸压力的上升速率达90 MPa/s以上;随点火延滞时间增加,最小点火能表现出先缓慢减小再急剧增大的规律;随粉尘质量浓度增加,最小点火能逐渐降低,当粉尘质量浓度超过500g/m3后逐渐趋于稳定。  相似文献   

11.
This paper experimentally investigated the relation between the minimum ignition energy (MIE) of magnesium powders as well as the effect of inert nitrogen (N2) on the MIE. The modified Hartmann vertical-tube apparatus and four kinds of different-sized pure magnesium powders (median particle size, D50; 28.1 μm–89.8 μm) were used in this study. The MIE of the most sensitive magnesium powder was 4 mJ, which was affected by the powder particle size (D50; 28.1 μm). The MIE of magnesium powder increased with an increase in the N2 concentration for the inerting technique. The magnesium dust explosion with an electrostatic discharge of 1000 mJ was suppressed completely at an N2 concentration range of more than 98%. The experimental data presented in this paper will be useful for preventing magnesium dust explosions generated from electrostatic discharges.  相似文献   

12.
针对某不饱和聚酯树脂钮扣厂在除尘设备维修过程中发生的粉尘爆炸事故,探究静电引起此次事故的可能性并提出防护措施。通过实验测定不饱和聚酯树脂钮扣粉尘的爆炸特性参数,进而确定其静电爆炸敏感性。结果发现:不饱和聚酯树脂钮扣粉尘云最小点火能MIE为4~10 mJ、最低着火温度MIT为480 ℃、粉尘层最低着火温度LIT>400 ℃。表明,此粉尘属易燃粉尘,其粉尘爆炸敏感度极高,被静电火花点燃的可能性极大,在生产过程中,应采取静电防护措施。  相似文献   

13.
采用MIE-D1.2型最小点火能测试装置及20 L球型粉尘爆炸测试装置,对苯乙烯丙烯酸共聚物/碳黑混合体系粉尘的爆炸特性进行研究。结果表明,过74μm、58μm、47μm孔径筛的粉尘对静电火花敏感,其最小点火能表征值分别为610 mJ、361 mJ、201 mJ。随粉尘质量浓度增加,最小点火能呈现先减小后增加的规律。随粉尘粒径减小,最小点火能与粉尘质量浓度变化关系曲线向低粉尘质量浓度和低点火能量方向偏移,且对应的最敏感爆炸质量浓度从500 g/m~3降至200 g/m~3。随粉尘质量浓度增加,过147μm、74μm、47μm孔径筛的苯乙烯丙烯酸共聚物/碳黑混合体系粉尘爆炸压力及爆炸压力上升速率呈现先增加后减小趋势。在相同粉尘质量浓度下,中位径小于74μm的苯乙烯丙烯酸共聚物/碳黑混合体系粉尘,粉尘的爆炸压力增幅明显减小。苯乙烯丙烯酸共聚物/碳黑混合体系粉尘爆炸下限质量浓度为25 g/m~3,最大爆炸指数为14.636 MPa·m/s,爆炸危险等级划分为St1。  相似文献   

14.
In this study, a physical model of the dust cloud ignition process is developed for both cylindrical coordinates with a straight-line shaped ignition source and spherical coordinates with a point shaped ignition source. Using this model, a numerical algorithm for the calculation of the minimum ignition energy (MIE) is established and validated. This algorithm can evaluate MIEs of dusts and their mixtures with different dust concentrations and particle sizes. Although the average calculated cylindrical MIE (MIEcylindrical) of the studied dusts only amounts to 63.9% of the average experimental MIE value due to reasons including high idealization of the numerical model and possible energy losses in the experimental tests, the algorithm with cylindrical coordinates correctly predicts the experimental MIE variation trends against particle diameter and dust concentration. There is a power function relationship between the MIE and particle diameter of the type MIE ∝ dpk with k being approximately 2 for cylindrical coordinates and 3 for spherical coordinates. Moreover, as dust concentration increases MIE(conc) first drops because of the decreasing average distance between particles and, at fuel-lean concentrations the increasing dust cloud combustion heat; however, after the dust concentration rises beyond a certain value, MIE(conc) starts to increase as a result of the increasingly significant heat sink effect from the particles and, at fuel-rich concentrations the no longer increasing dust cloud combustion heat.  相似文献   

15.
16.
To prevent high density polyethylene (HDPE) dust explosions, this study evaluated HDPE's explosive sensitivity characteristics, and comparatively examined two inert dust types (CaCO3 and NaHCO3) to mitigate the explosive sensitivity of HDPE dust. In the serials of experiments, the 1.2 L Hartmann tube and Godbert-Greenwald furnace were used respectively to measure the minimum ignition energy (MIE) and minimum ignition temperature (MIT) of HDPE dust. The findings demonstrated that the MIE and MIT of HDPE are 56.8 mJ and 320 °C under the most sensitive situation. Second, both CaCO3 and NaHCO3 can inhibit the explosive sensitivity of HDPE with the variation of several parameters (i.e., quality percentage and particle sizes). Specially, as the quality percentage of 38–48 μm NaHCO3 come to 70%, the HDPE/NaHCO3 will not be explosive. Finally, NaHCO3 had a better inerting effect than CaCO3 in the reduction of explosive sensitivity of HDPE.  相似文献   

17.
The temperature at which coal dust glows is normally much lower than the auto-ignition temperature (AIT) of methane/air mixtures, and thus a better understanding is needed regarding methane/air ignition in a heated environment in the presence of coal particles. A horizontal tube apparatus was used to test the effect of brown coal and two kinds of bituminous and anthracite on methane/air combustibility. For the four coal samples tested, the presence of coal particles significantly reduced the minimum temperature for ignition of methane/air mixtures in a heated environment. No. 1 bituminous coal with 12 mm diameter decreased the ignition temperature value from 595 to 500 °C. It is thought that pre-ignition of low-AIT volatiles emitted from the heated coal particles ignited the methane/air mixtures. Volatiles, sulfur content, and large porosity of piled coal particles all enhanced ignition of methane/air mixtures in a hot environment, while water content and small particle size reduced ignition. For anthracite, no ignition occurred when temperatures of the heated environment were lower than the AIT of methane (595 °C), except for the 12-mm-diameter sample. Anthracite did not readily ignite methane/air mixtures and the ignition mechanism was somewhat similar to that of a burning cigarette.  相似文献   

18.
To achieve the rapid prediction of minimum ignition energy (MIE) for premixed gases with wide-span equivalence ratios, a theoretical model is developed based on the proposed idea of flame propagation layer by layer. The validity and high accuracy of this model in predicting MIE have been corroborated against experimental data (from literature) and traditional models. In comparison, this model is mainly applicable to uniform premixed flammable mixtures, and the ignition source needs to be regarded as a punctiform energy source. Nevertheless, this model can exhibit higher accuracy (up to 90%) than traditional models when applied to premixed gases with wide-span equivalence ratios, such as C3H8-air mixtures with 0.7–1.5 equivalence ratios, CH4-air mixtures with 0.7–1.25 equivalence ratios, H2-air mixtures with 0.6–3.15 equivalence ratios et al. Further, the model parameters have been pre-determined using a 20 L spherical closed explosion setup with a high-speed camera, and then the MIE of common flammable gases (CH4, C2H6, C3H8, C4H10, C2H4, C3H6, C2H2, C3H4, C2H6O, CO and H2) under stoichiometric or wide-span equivalence ratios has been calculated. Eventually, the influences of model parameters on MIE have been discussed. Results show that MIE is the sum of the energy required for flame propagation during ignition. The increase in exothermic and heat transfer efficiency for fuel molecules can reduce MIE, whereas prolonging the flame induction period can increase MIE.  相似文献   

19.
Flammable aerosols have created many fire and explosion hazards in the process industry, but the flammability of aerosols has not been fully understood. The minimum ignition energy has been widely used as an indicator for flammability of combustible mixtures, but the amount of experimental data on the minimum ignition energy of aerosols is very limited. In this work, the minimum ignition energy of tetralin aerosols is predicted using an integrated model. The model applies the flame front propagation theory in aerosol systems to the growth of the flame kernel, which was created during the spark discharge in the ignition process. The aerosol minimum ignition energy was defined as the minimum level of energy in the initial flame kernel to maintain the kernel temperature above the minimum ignition temperature of 1073 K specific for tetralin aerosols during the kernel growth. The minimum ignition energy obtained in the model is influenced by the fuel-air equivalence ratio and the size of the aerosol droplets. For tetralin aerosols of 40 μm diameter, Emin decreases significantly from 0.32 mJ to 4.3 × 10 e−3 mJ when the equivalence ratio rises from 0.57 to 1.0. For tetralin aerosols of 0.57 equivalence ratio, Emin increases from as 0.09 mJ to 0.32 mJ when the droplet diameter rises from 10 μm to 60 μm. The trends are in agreement with previous experimental observations. The method used in current work has the potential to prediction of the minimum ignition energy of aerosol.  相似文献   

20.
The authors investigated the ignitability of aluminium and magnesium dusts that are generated during the shredding of post-consumer waste. The relations between particle size and the minimum explosive concentration, the minimum ignition energy, the ignition temperature of the dust clouds, etc. the relation between of oxygen concentration and dust explosion, the effect of inert substances on dust explosion, etc. were studied experimentally.

The minimum explosive concentration increased exponentially with particle size. The minimum explosive concentrations of the sample dusts were about 170 g/m3 (aluminium: 0–8 μm) and 90 g/m3 (magnesium: 0–20 μm). The minimum ignition energy tended to increase with particle size. It was about 6 mJ for the aluminium samples and 4 mJ for the magnesium samples. The ignition temperature of dust clouds was about 750 °C for aluminium and about 520 °C for magnesium. The lowest concentrations of oxygen to produce a dust explosion were about 10% for aluminium and about 8% for magnesium. A large mixing ratio (more than about 50%) of calcium oxide or calcium carbonate was necessary to decrease the explosibility of magnesium dust. The experimental data obtained in the present investigation will be useful for evaluating the explosibility of aluminium and magnesium dusts generated in metal recycling operations and thus for enhancing the safety of recycling plants.  相似文献   