首页 | 本学科首页   官方微博 | 高级检索  
     检索      


A method of analysis for gas explosions: H2Se case study
Institution:1. Department of Urology, University of Wisconsin School of Medicine and Public Health, Madison, WI;2. Department of Radiology, University of Wisconsin School of Medicine and Public Health, Madison, WI
Abstract:This paper presents a methodology for conducting a simplified gas-explosion analysis when there are uncertainties about the amount of fuel involved and the mode of combustion. The methodology is illustrated by a case study of an explosion of a cloud of hydrogen-selenide (H2Se), nitrogen and air. Hydrogen-selenide (H2Se) diluted with N2 is used in a reactor vessel to produce solar cells. An explosive mixture could be created if the reactor vessel failed and its contents mix with ambient air. Mixtures of 20% or 6% H2Se in N2 were considered as feedstock into the reactor. It was determined theoretically that an explosion involving either mixture would challenge the reactor room's integrity. However, it is unlikely that a local ignition will propagate in the dilute 6% H2Se mixture, because its adiabatic flame temperature is only 850 K; the 20% mixture is borderline flammable. Because of the proximity of personnel to the reactor room and the high toxicity of H2Se, any damage to the room boundary is considered unacceptable. To prevent accidental mixing of H2Se with air in the reactor, a nitrogen buffer was installed between the reactor vessel and the ambient air.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号