首页 | 本学科首页   官方微博 | 高级检索  
     检索      

计及黄安断面约束的宁夏电网外送能力研究
引用本文:摆世彬,宁 波,项 丽,耿天翔.计及黄安断面约束的宁夏电网外送能力研究[J].防灾减灾工程学报,2014(6):1-6.
作者姓名:摆世彬  宁 波  项 丽  耿天翔
作者单位:国网宁夏电力公司调度控制中心, 宁夏 银川 750001
摘    要:为了确定受黄安断面同杆 N-2 故障热稳限制的甘宁断面潮流外送能力,分析了宁夏电网各电源、负荷节点对黄安断面的灵敏度系数,建立了受黄安断面热稳限制和电源装机、负荷容量大小及同时率约束的甘宁断面外送模型,基于 MATLAB 的线性规划函数编写程序,计算了黄安断面极限功率下甘宁断面外送功率的极值。结果表明:在当前电网结构和负荷水平下,甘宁断面外送能力最大值大于甘宁断面热稳极限,最小值小于热稳极限的一半,且外送能力随中卫地区负荷增长以 3 倍速度下降。电力系统分析综合程序(PSASP)数值仿真计算验证了上述结论的正确性。

关 键 词:黄安断面    甘宁断面    灵敏度分析    线性规划算法    宁夏电网

Research on power transmission capacity of Ningxia power grid considering constraint of the Huanghe-Ningan section
BAI Shibin,NING Bo,XIANG Li,GENG Tianxiang.Research on power transmission capacity of Ningxia power grid considering constraint of the Huanghe-Ningan section[J].Journal of Disaster Prevent and Mitigation Eng,2014(6):1-6.
Authors:BAI Shibin  NING Bo  XIANG Li  GENG Tianxiang
Institution:Dispatch & Control Center of Sate Grid Ningxia Power Co.,Yinchuan Ningxia 750001 ,China
Abstract:In order to ascertain the transmission capability of power tidal current in Gansu-Ningxiasection considering the thermal stability limit under N-2 fault on the same transmission tower ofHuanghe-Ningan section,the sensitivity coefficient of electrical sources and load nodes of Ningxiapower grid for Huanghe-Ningan section are analyzed,the Gansu-Ningxia section delivery model isestablished based on constraints of the Huanghe-Ningan section heat stability limit,the power plantinstallation and load capacity and simultaneity factor. Based on linear programming function ofMATLAB,the transmission power extremum of Gansu -Ningxia section is calculated under theultimate power of Huanghe -Ningan section. The result shows that the maximum value oftransmission capability of Gansu -Ningxia section is greater than the Gansu Ningxia section heatstability limit,and the minimum value is less than half of the thermal stability limit,and along withthe load growth of the Zhongwei area,the power transmission capability fall at a speed of 3 times.The correctness of the above conclusion is verified by the numerical simulation calculation based onpower system analysis synthetic program(PSASP).
Keywords:
点击此处可从《防灾减灾工程学报》浏览原始摘要信息
点击此处可从《防灾减灾工程学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号