Effect of rusting and mechanical damage of gap surfaces on efficiency of flame gaps in flameproof electrical apparatus
Authors:F Solheim  BJ Arntzen  RK Eckhoff
Institution:1. CERFACS, 42 Avenue Gaspard Coriolis, Toulouse Cedex 01 31057, France;2. Renault SAS, 1 Avenue du Golf, Guyancourt Cedex 78288 France;3. CNRS, IMFT, 1 Allée du Professeur Camille Soula, Toulouse Cedex 31400 France;1. Laboratory for Simulation and Modelling of Particulate Systems, Department of Chemical Engineering, Monash University, VIC 3800, Australia;2. School of Chemical Engineering, University of New South Wales, NSW 2052, Australia
Abstract:Potentially incendiary electrical apparatus for use in the presence of explosive gas atmospheres have to be specially designed to prevent the apparatus from igniting the gas. Flameproof design is one of several options, and one requirement is then that any holes and gaps in the enclosure wall be designed to prevent a gas explosion inside the enclosure from being transmitted to an explosive gas cloud outside it. Current standards (IEC) require that flame gap surfaces have a surface roughness of <6.3 μm. Any damaged flame gap surface has to be restored to this quality. The present investigation has demonstrated that flame gap surfaces in flameproof electrical apparatuses can suffer considerable corrosive and mechanical damage without any reduction of gap performance. In some cases very significant mechanical surface damage in fact improves gap performance. Possible physical reasons for this are discussed. These findings indicate that current high costs of repairing and replacing flameproof electrical apparatus in process plants offshore and onshore can be significantly reduced without any increase of explosion risks.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号