首页 | 本学科首页   官方微博 | 高级检索  
     

多传感器耦合区域火灾报警技术研究
引用本文:王静舞,关劲夫,于淼淼,袁宏永,陈涛,刘小勇,王军. 多传感器耦合区域火灾报警技术研究[J]. 火灾科学, 2020, 29(4): 233-240. DOI: 10.3969/j.issn.1004-5309.2020.04.05
作者姓名:王静舞  关劲夫  于淼淼  袁宏永  陈涛  刘小勇  王军
作者单位:清华大学合肥公共安全研究院,合肥,230061;清华大学工程物理系公共安全研究院,北京,100084;清华大学合肥公共安全研究院,合肥,230061;清华大学工程物理系公共安全研究院,北京,100084
摘    要:早期预警与低误报率一直是建筑火灾探测面临的挑战与难题.已有研究多针对特殊场所特定燃烧产物或多种传感器耦合,普适性不强,探测设备成本高,无法大规模应用.通过将火灾烟气蔓延规律与探测器信号时空分布融合,在不增加探测器数量和分布的情况下,提出了一种基于建筑结构微元的多传感器耦合区域火灾报警模型.对典型火灾场景的烟气蔓延情况进...

关 键 词:火灾探测  烟气蔓延  误报率  多传感器  建筑结构微元

Study on multi-sensor coupling regional fire alarm technology
WANG Jingwu,GUAN Jinfu,YU Miaomiao,YUAN Hongyong,CHEN Tao,LIU Xiaoyong,WANG Jun. Study on multi-sensor coupling regional fire alarm technology[J]. Fire Safety Science, 2020, 29(4): 233-240. DOI: 10.3969/j.issn.1004-5309.2020.04.05
Authors:WANG Jingwu  GUAN Jinfu  YU Miaomiao  YUAN Hongyong  CHEN Tao  LIU Xiaoyong  WANG Jun
Affiliation:Hefei Institute for Public Safety Research, Tsinghua University, Hefei 230061, China;Institute of Public Safety Research, Department of Engineering Physics, Tsinghua University, Beijing 100084, China
Abstract:Early warning and low false alarm rate have always been the challenges and problems in building fire detection. Previous research mostly focuses on specific combustion products or coupling multiple sensors in special places, which is not universal. The cost of detection equipment is high, and it cannot be applied on a large scale. This paper proposes a multi-sensor coupled regional fire alarm model based on the building structure micro-elements by combining the fire smoke spread characteristic with the spatial and temporal distribution of detector signal, without increasing the number of detectors. The fire smoke spread of typical fire scenarios was simulated and analyzed. The signal intensity of the detector in a long and narrow structure had a certain regularity. After applying the regional fire alarm model, the alarm time was 14.7% earlier than the traditional model, eliminating the problem of building fire alarms caused by false alarms from a single detector. The results show that the multi-sensor coupling detection mode significantly shortens the fire alarm time, reduces the false alarm rate of fire detection, and achieves accurate early identification and early warning of fire.
Keywords:Fire detection   Smoke spread   False alarm rate   Multi-sensor   Building structure micro-element
本文献已被 万方数据 等数据库收录!
点击此处可从《火灾科学》浏览原始摘要信息
点击此处可从《火灾科学》下载全文