首页 | 本学科首页   官方微博 | 高级检索  
     检索      

聚集用火下热探测器响应温度的研究
引用本文:田水承,张成镇.聚集用火下热探测器响应温度的研究[J].中国安全生产科学技术,2018,14(2):52-57.
作者姓名:田水承  张成镇
作者单位:(1. 西安科技大学 安全科学与工程学院安全管理研究所,陕西 西安 710054; 2. 西安科技大学 教育部西部矿山开采及灾害治理重点实验室,陕西 西安 710054)
摘    要:为得出聚集用火下建筑物天花板平面热探测器响应温度的计算公式,采用PyroSim 2015软件进行建模,在模型天花板平面内设置一系列的热电偶代替热探测器监测温度变化,在热释放速率(HRR)分别为1,5,10,20,30 kW和天花板高度分别为3,5,7 m的条件下进行15次数值模拟,对模拟结果数据分析、处理及拟合。研究表明:羽流中心线处温度远高于其他位置;羽流中心线处响应温度随着天花板高度的升高而降低,且与HRR存在显著的二次函数关系;其他位置处响应温度随着天花板高度的升高而降低,随着到羽流中心线距离的增大而降低,且与HRR和到羽流中心线的距离存在显著的二次函数关系。结合室内全年最高温度及补偿温度,建立出聚集用火下热探测器响应温度的计算公式。

关 键 词:计算公式  聚集用火  热探测器响应温度  PyroSim  数值模拟

Research for response temperature of thermal detector in clustered using fire
TIAN Shuicheng,,ZHANG Chengzhen,.Research for response temperature of thermal detector in clustered using fire[J].Journal of Safety Science and Technology,2018,14(2):52-57.
Authors:TIAN Shuicheng    ZHANG Chengzhen  
Institution:(1. College of Safety Science and Engineering, Xi’an University of Science and Technology, Xi’an Shaanxi 710054, China; 2. Key Laboratory of Western Mines and Hazard Prevention of Ministry of Education, Xi’an University of Science and Technology, Xi’an Shaanxi 710054, China)
Abstract:To obtain the calculation formula for the response temperature of thermal detector on the ceiling plane of the buildings with the clustered using fire, the modeling was carried out by using PyroSim 2015 software. A series of thermocouples were set on the ceiling plane of the model instead of the thermal detectors to monitor the temperature change, and 15 numerical simulation were conducted when the heat release rate (HRR) was 1, 5, 10, 20, 30 kW respectively and the ceiling height was 3, 5, 7 m respectively, then the data of simulation results were analyzed, processed and fitted. The results showed that the temperature at the center line of the plume was much higher than those at the other locations. The response temperature at the center line of the plume decreased with the increase of ceiling height, and it had a significant quadratic function relationship with the HRR. The response temperature at the other locations decreased with the increase of ceiling height and decreased with the increasing distance to the center line of the plume, and it had a significant quadratic function relationship with the HRR and the distance to the center line of the plume. A calculation formula for the response temperature of thermal detector in clustered using fire was established by combining with the indoor annual maximum temperature and compensation temperature.
Keywords:calculation formula  clustered using fire  thermal detector’s response temperature  PyroSim  numerical simulation
本文献已被 CNKI 等数据库收录!
点击此处可从《中国安全生产科学技术》浏览原始摘要信息
点击此处可从《中国安全生产科学技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏