首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Indoor air quality assessment in child care and medical facilities in Korea
Authors:Ehsanul Kabir  K-H Kim  Jong Ryeul Sohn  Bo Youn Kweon  Jong Hyun Shin
Institution:Department of Environment & Energy, Sejong University, Seoul, South Korea.
Abstract:In order to characterize the status of indoor air pollution in some important facilities, a list of key criteria pollutants particulate matter (PM(10)), carbon dioxide (CO(2)), carbon monoxide (CO), formaldehyde (HCHO), and bioaerosol] was measured from a total of 91 randomly selected sites in 18 different cities, Korea (February 2006 to December 2009). The target facilities include 43 child care facilities, 38 medical facilities, 6 elementary schools, and 4 postnatal care centers. The results showed that some air pollutants (e.g., CO and HCHO) did not exceed the recommended guideline e.g., the Korean indoor air standard (KIAS) values of 10 ppm and 100 ppb, respectively]. However, concentration of PM(10), CO(2), and bioaerosol occasionally exceeded their respective guidelines (e.g., seven, three, and two cases). Discrete seasonalities were observed from indoor pollutants because of varying ventilation practice (e.g., summer time dominance of PM(10), HCHO, and bioaerosol or winter dominance of CO(2) and CO). However, as the concentrations of the indoor pollutants were scarcely above the recommended guideline level, more diversified approaches are desirable to diagnose the status of indoor pollution and to provide a realistic strategy for the improvement of IAQ.