摘    要:利用微型燃烧量热计(MCC)、热重分析(TGA)、实时红外光谱(RTFTIR)以及热重-红外联用技术(TG-FT-IR)研究了PVC电缆料老化前后火灾危险性的变化。MCC结果表明,老化后的PVC的最大热释放速率增加了56.3%,总热释放量从10.6kJ/g增加到16.8kJ/g,点燃温度也由302℃提前到282℃。TG-FTIR和RTFTIR的分析结果显示,PVC的主要降解产物有水、碳氢化合物、二氧化碳和一氧化碳。PVC达到最大降解速率的温度约为240℃,与MCC、TG的结果相符合。PVC的裂解气体中包含CO2和CO,还有剧毒气体HCl。这些实验数据说明PVC材料在使用过程中火灾危险性加大,为老城区电气线路和设备的改造提供了理论依据和实验基础。

关 键 词:聚氯乙烯电缆料  老化  火灾危险性
收稿时间:2010/11/12 0:00:00
修稿时间:2010/12/16 0:00:00

Study on fire hazard of pre-aging and post-aging PVC cable materials
LI Zai-hui,HU Yuan,SONG Lei,WANG Xin,FENG Hao and JIE Gan-xin.Study on fire hazard of pre-aging and post-aging PVC cable materials[J].Fire Safety Science,2011,20(1):56-61.
Authors:LI Zai-hui  HU Yuan  SONG Lei  WANG Xin  FENG Hao and JIE Gan-xin
Institution:1.State Key Lab of Fire Science,University of Science and Technology of China,Hefei,Anhui,230026,China;2.Mawei Fire Protection Battalion of Chinese People's Armed Police Force,Fuzhou,Fujian,350015,China;3.State Key Lab of Environmental Adaptability for Industrial Products,China National Electric Apparatus Research Institute,Guangdong,Guangzhou,510300,China)
Abstract:The fire hazard of pre-aging and post-aging PVC cable materials was investigated using microscale combustion calorimetry(MCC),thermogravimetric analysis(TGA),thermogravimetric analysis-infrared spectrometry(TG-FTIR) and real time FTIR.MCC data indicated that the peak heat release rate(PHRR) of post-aging PVC cable materials increased by 56.3% compared to pre-aging PVC cable materials,the total heat release increased from 10.6 kJ/g to 16.8kJ/g and the ignition temperature decreased from 302℃ to 282℃.The TG-FTIR and RTFTIR results suggested that the main pyrolysis products of PVC cable materials were water,hydrocarbons,CO2,CO,et al.The maximum decomposition rate of PVC cable materials appeared at around 240℃,which corresponded well with MCC and TGA.The pyrolysis products of PVC cable materials contained CO2,CO and toxic HCl.It is concluded that the fire hazard of PVC cable materials increases during the course of use.