Abstract:Electrical apparatus for use in the presence of explosive gas atmospheres has to be specially designed to prevent the apparatus from igniting the gas. Flameproof design is one of several options, and one requirement is then that any holes and slits in the enclosure wall be designed to prevent a possible gas explosion inside the enclosure from being transmitted to an explosive gas cloud outside it. Current standards (IEC) require that joint surfaces have a surface roughness of <6.3 μm. Any damaged joint surface has be restored to this quality. The present investigation has demonstrated that flame gap surfaces in flameproof electrical apparatuses can suffer considerable mechanical and corrosive damage before the flame gaps no longer function satisfactorily. In some cases very significant mechanical surface damage in fact improves the gap performance. This indicates that current high costs of repairing and replacing flameproof electrical apparatus in process plants offshore and onshore can be reduced considerably without any increase of the explosion risk.
Keywords:Gas explosions  Flame transmission  Re-ignition  Electrical apparatus  Flameproof design  Flame gap damage