一起800kV罐式断路器绝缘故障判断分析
引用本文:康,真.一起800kV罐式断路器绝缘故障判断分析[J].防灾减灾工程学报,2013(4):29-31.
作者姓名:  
作者单位:国网宁夏电力公司检修公司, 宁夏 银川 750011
摘    要:针对黄河变电站设备运行过程中发生的一起800 kV罐式断路器绝缘故障,通过现场试验及解体检查等方法进行分析,找出了故障发生的原因。分析结果表明:断路器盆式绝缘子根部存在残留异物或凝露,导致运行中放电击穿,是造成断路器绝缘故障的根本原因。

关 键 词:800  kV    罐式断路器    绝缘故障

Analysis on insulation fault judgement of 800 kV tank-type circuit breaker
KANG Zhen.Analysis on insulation fault judgement of 800 kV tank-type circuit breaker[J].Journal of Disaster Prevent and Mitigation Eng,2013(4):29-31.
Authors:KANG Zhen
Institution:Maintenance Filiale of Ningxia Electric Power Corporation, Yinchuan Ningxia 750011 , China
Abstract:Aiming at a insulation fault of 800 kV tank-type circuit breaker in Huanghe River Sub?station, through the locale test and disassembly check, finds out the faults causes of circuit breaker.The analysis result shows that the root of basin-type insulator of circuit breaker exist residuum or con?densation bringing on it discharge breakdown in operation is the basic reason of the circuit breaker in?sulation fault.