首页 | 本学科首页   官方微博 | 高级检索  
     检索      

太阳山换流站背景谐波的测量与计算
引用本文:范偲偲,黄永宁,张爽,梁剑,黄欣.太阳山换流站背景谐波的测量与计算[J].防灾减灾工程学报,2015(6):21-24.
作者姓名:范偲偲  黄永宁  张爽  梁剑  黄欣
作者单位:北方民族大学,宁夏银川 750021;国网宁夏电力公司电力科学研究院,宁夏银川 750011;国网宁夏电力公司检修公司,宁夏银川 750011
摘    要:为了满足太阳山换流站滤波器设计对电网背景谐波数据的要求,对2013年宁夏电网与太阳山密切相关的变电站进行全面的背景谐波测试,通过实测谐波数据与网架潮流计算数据的一致性分析,验证了计算方法的可行性和准确性;考虑系统网架变化,将太阳山换流站接入系统,同时考虑新能源、谐波源、网架和负荷的发展,计算得出2016年太阳山换流站750 kV母线谐波电压值,并在此基础上,给出了有一定裕度的推荐值供设计单位采用。

关 键 词:背景谐波  750kV换流站  滤波器  潮流计算

Measurement and calculation on background harmonic of Taiyangshan converting substation
Fan,Huang Yongning,Zhang Shuang,Liang Jian,Huang Xin.Measurement and calculation on background harmonic of Taiyangshan converting substation[J].Journal of Disaster Prevent and Mitigation Eng,2015(6):21-24.
Authors:Fan  Huang Yongning  Zhang Shuang  Liang Jian  Huang Xin
Institution:North Nationality University, Yinchuan Ningxia 750021 , China;Power Research Institute of State Grid Ningxia Power Co., Yinchuan Ningxia 75001 1 ,China; Maintenance Filiale of Ningxia Power Co., Yinchuan Ningxia 750011 , China
Abstract:In order to meet the demand of the filter design in Taiyangshan converting substation forbackground harmonic data of the power grid, makes complete background harmonic test of the substationsclosely related with Taiyangshan in Ningxia power grid in 2013. By analyzing theconsistency between practical measured harmonic data and network frame power flow calculationdata, verifies the feasibility and accuracy of the calculation method; considering the change ofsystemnetwork frame ,access the Taiyangshan converting substationintopower system ,Simultaneously taking into account the development of new energy, harmonic source , network frameand load, calculates and obtains 750 kV bus harmonic voltage values of Taiyangshan convertingsubstation in 2016, on this basis, provides a certain margin recommended values for filter designer.
Keywords:
点击此处可从《防灾减灾工程学报》浏览原始摘要信息
点击此处可从《防灾减灾工程学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号