363kV快速真空断路器电场计算
引用本文:艾绍贵,余晓,刘恒,黄永宁,罗海荣,于浩,李全明.363kV快速真空断路器电场计算[J].防灾减灾工程学报,2019(3):1-6.
作者姓名:艾绍贵  余晓  刘恒  黄永宁  罗海荣  于浩  李全明
作者单位:国网宁夏电力有限公司电力科学研究院,宁夏银川 750011;重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆 400044;安徽徽电科技股份有限公司,安徽合肥 230088
基金项目:国家电网公司总部科技项目(5229DK160005)
摘    要:高电压等级开关设备的绝缘水平严重影响设备的安全运行和开断能力,因此在研发高电压真空断路器时需要分析其电场分布。以363 kV快速真空断路器设计结构为原型,建立三维有限元电场计算模型,分别计算了额定电压下闭合和开断工况下的电场分布,分析了灭弧室、绝缘子以及主要金具表面的电场大小。结果表明:均压环表面电场最大值为1.92 MV/m,绝缘子表面最大值为0.36 MV/m,开距20 mm时灭弧室断口电场最大值为3.5 MV/m,其他部位电场均处于控制范围内,断路器总体结构设计合理,满足绝缘要求。

关 键 词:多断口  真空断路器  有限元  电场计算

Electric field calculation of 363 kV fast vacuum circuit breaker
AI Shaogui,YU Xiao,LIU Heng,HUANG Yongning,LUO Hairong,YU Hao,LI Quanming.Electric field calculation of 363 kV fast vacuum circuit breaker[J].Journal of Disaster Prevent and Mitigation Eng,2019(3):1-6.
Authors:AI Shaogui  YU Xiao  LIU Heng  HUANG Yongning  LUO Hairong  YU Hao  LI Quanming
Institution:Power Research Institute of State Grid Ningxia Electric Power Co ,Ltd , Y inchuan Ningxia 750011 , China;State Key Laboratory of Power Transmission Equipment & System Security and New Technology , ChongqingUniversity , Chongqing 400044 , China;Anhui Huidian Technology Co , Ltd , Hefei Anhui 230088 , China
Abstract:The insulation level of high-voltage switchgear will affect the safe operation and breakingcapacity of the equipment. Therefore, it is necessary to analyze the electric field distribution whendeveloping high-voltage vacuum circuit breakers ( VCB). Based on the prototype structure of363 kV fast VCB, a three-dimensional finite element electric field calculation model was estab-lished. The electric field distribution of closed and open state with rated voltage were calculatedrespectively. The electric field of the arc extinguishing chamber, insulator and main fittings were ana-lyzed. The results show that the maximum electric field of grading rings, and post insulator are1.92 MV/m and 0.36 MV/m respectively. The maximum electric field of break is 3.5 MV/m at the open gaps of 20 mm. Electric field of other parts are within the limitation. The overall structure of the circuit breaker is designed reasonably to meet the insulation requirements.