Environmental Technology Verification (ETV) test of dioxin emission monitors
Authors:Chun Wai Lee  Dennis G Tabor  Kenneth A Cowen
Institution:(1) Air Pollution Prevention and Control Division (E305-01), National Risk Management Research Laboratory, Office of Research and Development, United States Environmental Protection Agency, 109 T.W. Alexander Drive, Research Triangle Park, NC 27711, USA;(2) Battelle, Columbus, OH, USA
Abstract:The performance of four dioxin emission monitors, including two long-term sampling devices, the Dioxin-MonitoringSystem (DMS) and AMESA (the adsorption method for sampling dioxins and furans), and two semireal-time continuous monitors, the resonance ionization with multimirror photon accumulation time-of-flight mass spectrometer (RIMMPA-TOFMS) and the jet resonance-enhanced multiphoton ionization (jet-REMPI) system were tested. A package boiler burning a simulated chlorinated hazardous waste was used for a total of nine tests. Reference samples were collected during each test and analyzed for polychlorinated dibenzodioxins and dibenzofurans (PCDDs/Fs) using gas chromatography mass spectrometry. The PCDD/F concentrations of the reference samples measured by EPA Method 23 ranged from 0.9 to 6.0 ng toxic equivalence (TEQ)/dry standard cubic meter. The relative accuracies achieved by DMS, AMESA, and jet-REMPI varied from 22.6% to 78.2%, with 100% data completeness. The RIMMPA-TOFMS produced no quantifiable results due to various difficulties associated with the instrument during the testing. The two long-term samplers were easy to install and operate and provided a cumulative, averaged emission for the sampling period. The operations of the two semi-real-time continuous monitors were relatively complex, but one of them provided on-site, real-time data for PCDD/F emissions from measurement of a TEQ correlative indicator compound. This article summarizes results from the individual Environmental Technology Verification reports for the four dioxin monitors. This work was presented, in part, at the Fourth International Conference on Combustion, Incineration/Pyrolysis and Emission Control (i-CIPEC)
Keywords:Continuous emission monitor  Dioxins  PCDDs/Fs  POPs  Incineration emissions
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号