A series of experiments on explosion venting of methane-air mixtures are performed to scrutinize the pressure evolution as well as the flame dynamics and morphology at various vent conditions. Specifically, a premixed flame is ignited at the center of a polycarbonate cylindrical compartment, with three various vent areas considered (with negligible vent relief pressure). As expected, the highest maximum pressure is observed in the case of the smallest vent area. For all three cases, the pressure evolution experiences two major peaks, associated with the instants (i) when the maximum flame front surface area in the chamber is reached and (ii) when an external explosion occurs due to venting of unburned gases, respectively. For the fuel-rich mixtures, a flashback is observed subsequent to the external explosion, constituting the key outcome of the present work. The flame tip velocities show two general trends, namely, exponential acceleration towards the vent, while a flame propagates towards the blocked side of the compartment with no acceleration, which is important to know in the fire/explosion safety applications.  相似文献   

2.
为了减少管内气体爆炸造成的损失与破坏,基于大涡模拟LES模型和Zimont燃烧模型,研究泄爆尺寸(直径为40,60,80 mm)和泄爆位置(侧方距点火端1,3,5 m)等泄爆条件对受限空间中氢气燃爆特性的影响。研究结果表明:大孔径泄爆口更好的排放效果造成火焰锋面在通过泄爆口时发生严重畸变,而泄爆口与点火端距离的增加则会削弱火焰锋面畸变的程度,且不同尺寸泄爆口产生的泄压效果差异较大。因此,应考虑将合适尺寸的泄爆口设置于靠近易燃点处。通过探索不同泄爆孔径与泄爆口位置对氢气火焰传播的影响规律,可为实际应用中的安全泄爆起到指导性作用。  相似文献   

3.
加气站压缩机间气体爆炸数值模拟研究   总被引:1,自引:0,他引:1  
加气站压缩机间安全设计时,需要评估内部气体爆炸危害,确定爆炸能量和影响因素。采用CFD技术,建立加气站压缩机间三维模型,模拟不同点火源位置、泄压板不同泄压压力和重量下,压缩机间气体爆炸时的爆炸压力及火焰传播行为。结果表明点火源位置以及泄压参数是影响加气站压缩机间气体爆炸的重要因素;点火源位置距离压缩机间放空位置越近,爆炸压力越小;对于泄压参数,爆炸压力与泄压板开启压力和重量之间均为正比关系。为减缓压缩机间内的气体爆炸危害,需要合理布置点火源位置,选择容重轻、泄压压力小的泄压材料,并同时需要考虑爆炸导致的物体破碎危害以及火焰次生灾害。  相似文献   

4.
利用球型容器与管道组合,开展连通容器气体爆炸与泄爆实验,分析连通条件下,火焰在管道中的传播过程及其对起爆容器和传爆容器的压力影响。实验结果表明:连通容器气体爆炸中,火焰从起爆容器到传爆容器传播经历了一段不断加速,但加速度不断减小的过程;泄爆过程中,火焰传播过程与密闭爆炸时基本一致。管道中火焰加速传播,使得传爆容器的爆炸压力和强度相较于作为起爆容器时均明显增加,危险更大,采用与起爆容器相同的泄爆面积,无法满足对连通容器中传爆容器的泄爆。同时,泄爆是一个快速的能量泄放过程应选择合理的泄爆方式,防止二次危害。  相似文献   

5.
To develop the application of explosion venting technology in high-pressure vessels, a new model for the design of dust explosion venting size was presented, which took the physicochemical phenomenon deriving from the elevation of the static activation pressure into account. Firstly, for confined pressure rise, the wall quenching effect originating from the dust flame thickness was considered by adopting the three-zone model. Secondly, for the venting pressure rise, the energy loss due to the discharge of high-energy burnt mixture (quantified as the specific surface area loss of the flame) was taken into account and the induced turbulence factor was introduced. Thirdly, for the venting pressure drop, a dynamic pressure relief capability evaluation model which takes into account the flame morphology evolution (tear-shaped flame) and the proportion of discharged mixture (relative volume ratio) at elevated activation pressure was proposed. The predicted maximum reduced pressure and venting size were checked against the PMMA explosion experiments and a more great performance was obtained compared with standards.  相似文献   

6.
Explosion venting is widely applied in industrial explosion-proof designs due to the convenient, economical and practical features of this method. Natural gas is usually stored in storage tanks. If the gas in the vessel is mixed with air and encounters an ignition source, explosion venting might occur, producing jet fire, generating new secondary derivative accidents and causing casualties and property losses. In this paper, a set of test platforms including wire-mesh suppression devices is established to study the inhibition of jet fire induced by explosion venting by wire mesh. The experimental research shows that a wire mesh significantly inhibits the jet fire induced by explosion venting. The flame propagation velocity and pressure clearly decrease with increasing numbers of wire-mesh layers. The wire-mesh structure significantly affects the flame propagation, and the more layers of mesh there are, the better the suppression effect is. The flame temperature gradually decreases with the addition of the wire mesh. The mesh size significantly affects the pressure propagation of explosion venting. The explosion pressure gradually decreases with the addition of the wire mesh. With increasing distance between the wire mesh and the explosion vent, the maximum temperature first increases and then decreases, and the maximum explosion pressure first decreases and then increases. In the case of single gas cloud, the flame suppression effect is the most obvious when the wire mesh is 0.2 m away from the explosion vent. In the case of double gas clouds, the flame suppression effect is the most significant when the distance between the wire mesh and the first gas cloud is 0.4 m.  相似文献   

7.
A study of vented explosions in a length over diameter (L/D) of 2 in cylindrical vessel connecting with a vent duct (L/D = 7) is reported. The influence of vent burst pressure and ignition locations on the maximum overpressure and flame speeds at constant vent coefficient, K of 16.4 were investigated to elucidate how these parameters affect the severity of a vented explosion. Propane and methane/air mixtures were studied with equivalence ratio, Φ ranges from 0.8 to 1.6. It is demonstrated that end ignition exhibited higher maximum overpressures and flame speeds in comparison to central ignition, contrary to what is reported in literature. There was a large acceleration of the flame toward the duct due to the development of cellular flames and end ignition demonstrated to have higher flame speeds prior to entry into the vent due to the larger flame distance. The higher vent flow velocities and subsequent flame speeds were responsible for the higher overpressures obtained. Rich mixtures for propane/air mixtures at Φ = 1.35 had the greatest flame acceleration and the highest overpressures. In addition, the results showed that Bartknecht's gas explosion venting correlation is grossly overestimated the overpressure for K = 16.4 and thus, misleading the impact of the vent burst pressure.  相似文献   

8.
Flameless venting is a sort of dual mitigation technique allowing, in principle, to vent a process vessel inside a building where people are working without transmitting a flame outside the protected vessel. Existing devices are an assembly of a vent panel and a metal filter so that the exploding cloud and the flame front is forced to go through the filter. Within the frame of ATEX Directive, those systems need to be certified. To do so a standard (NF EN 16009) has been issued describing which criteria need to be verified/measured. Among them, the “efficiency” factor as defined earlier for standard vents. This implies that flameless venting systems are basically considered as vents. But is it really so? This question is discussed on the basis of experimental results and some implications on the practical use and certification process are drawn. The practical experience of INERIS in testing such systems is presented in this paper. Schematically, with a flameless vent the pressure is discharged but not the flame so that combustion is proceeding to a much longer extent inside the vessel than with a classical vent so that the physics of the explosion is different. In particular it is shown that besides the problem of the unloading of the confined explosion, there is a highly complicated fluid mechanics problem of a fluid-particle flow passing through a porous media (the flameless device grids arrangement in the filter), which passing surface is progressively reduced. To characterize Flameless venting the problem can be addressed sequentially, considering separately the vent panel and the flameless mesh. A model is proposed to estimate the overall venting efficiency of the flameless vent. However, it does not address the flame quenching issue, which is a different problem of heat exchange between the devices and the evacuated burnt products.  相似文献   

9.
Explosion venting is a frequently-used way to lower explosion pressure and accident loss. Recently, studies of vessel explosion venting have received much attention, while little attention has been paid to pipe explosion venting. This study researched the characteristics of explosion venting for Coal Bed Methane (CBM) transfer pipe, and proposed the way of explosion venting to chamber in order to avoid the influence of explosion venting on external environment, and investigated the effects of explosion venting to atmosphere and chamber. When explosion venting to atmosphere, the average explosion impulse 4.89 kPa s; when explosion venting to 0 MPa (atmospheric pressure) chamber, average explosion impulse is 7.52 kPa s; when explosion venting to −0.01 MPa chamber, explosion flame and pressure obviously drop, and average explosion impulse decreases to 4.08 kPa s; when explosion venting to −0.09 MPa chamber, explosion flame goes out and average explosion impulse is 1.45 kPa s. Thus, the effect of explosion venting to negative chamber is far better than that to atmospheric chamber. Negative chamber can absorb more explosion gas and energy, increase stretch of explosion flame, and eliminate free radical of gas explosion. All these can promote the effect of explosion venting to negative chamber.  相似文献   

10.
The effect of the vent burst pressure on explosion venting of a rich methane-air mixture was experimentally investigated in a small cylindrical vessel. The experimental results show that Helmholtz oscillation of the internal flame bubble of the methane-air mixture can occur in a vessel with a vent area much smaller than that reported by previous researchers, and the period of Helmholtz oscillation decreases slightly when the vent burst pressure increases. The maximum overpressure in the vessel increases approximately linearly with the increase in the vent burst pressure; however, the pressure peaks induced by Helmholtz oscillation always remain approximately several kilopascals. The external flame reaches its maximum length in a few milliseconds after vent failure and then oscillates in accordance with the pressure oscillation in the vessel. The maximum length of the external flame increases, but its duration time decreases with the increase in the vent burst pressure.  相似文献   

11.
Dust explosion venting experiments were performed using a 20-L spherical chamber at elevated static activation overpressures larger than 1 bar. Lycopodium dust samples with mean diameter of 70 μm and electric igniters with 0.5 KJ ignition energy were used in the experiments. Explosion overpressures in the chamber and flame appearances near the vent were recorded simultaneously. The results indicated that the flame appeared as the under-expanded free jet with shock diamonds, when the overpressure in the chamber was larger than the critical pressure during the venting process. The flame appeared as the normal constant-pressure combustion when the pressure venting process finished. Three types of venting processes were concluded in the experiments: no secondary flame and no secondary explosion, secondary flame, secondary explosion. The occurrence of the secondary explosions near the vent was related to the vent diameter and the static activation overpressure. Larger diameters and lower static activation overpressures were beneficial to the occurrence of the secondary explosions. In current experiments, the secondary explosions only occurred at the following combinations of the vent diameter and the static activation overpressure: 40 mm and 1.2 bar, 60 mm and 1.2 bar, 60 mm and 1.8 bar.  相似文献   

12.
To further understand the dynamic mechanism of dust explosion through a vent duct, we designed a small-scale cylindrical vessel connected with a vent duct and performed a dust explosion venting experiment under different opening pressures using corn starch as the explosive medium in this study. The results show that weakening effect of duct on venting is positively correlated with the opening pressure. The explosion pressure in the duct presents a three-peak-structure with time, successively caused by the membrane breaking shock wave, the secondary explosion in the tube, and the continuous combustion, and decreases gradually with the propagation distance. Meanwhile, the three pressure peaks are positively correlated with the opening pressure, while the time interval between them goes to contrary. The increase of opening pressure leads to the increase of secondary explosion intensity and reverse flow in the vessel, further accelerates the reaction rate in the vessel, and then shortens the duration of combustion in the vessel until the phenomenon of flame reignition in the vessel disappears.  相似文献   

13.
为揭示泄爆面特征参数对大尺度受限空间内天然气爆炸超压峰值结构的影响机制,基于典型房间特征,借助计算流体动力学技术研究不同泄爆面开启压力、开启时间以及泄压比等参数条件下室内天然气泄爆超压峰值结构的分布规律。研究结果表明:峰值Pb随开启压力和开启时间增加均呈线性增长趋势,而泄压比对Pb影响较小;峰值Pmfa与室内最大火焰面积有关,随开启压力、开启时间的增加和泄压比的减小,气体出流速度增大,进而产生更强的湍流,导致室内火焰面积和气体燃烧率增加,最终Pmfa增大;峰值Pext随泄压比增加呈快速降低趋势,同时开启压力和开启时间对Pext影响具有协同效应,共同促进Pext快速增加。  相似文献   

14.
为研究泄爆面积比对泄爆门泄爆特性的影响,运用FLUENT软件建立煤矿井下1∶1巷道模型,在不同泄爆面积比的工况下对瓦斯爆炸传播规律及泄爆过程进行模拟,分析其变化特征和封闭泄爆效果。结果表明:S0工况条件下,压力和温度衰减后保持在0.29 MPa和565 K;S1~S4工况条件下,S4比S1,S2和S3达到封闭状态时间快780,260,50 ms,封闭时间最大节省70.91%;随着泄爆面积比的增大,封闭火区内的压力的峰值、峰值数量和达到封闭状态时间减小,泄爆能力增强;火焰速度峰值和衰减速率增大;温度的初始峰值、峰值数量和达到稳定状态时间减小,最大峰值反而增大,说明泄爆门对瓦斯爆炸火焰无抑制作用。  相似文献   

15.
A model of explosion pressure build up in enclosures with translating inertial vent covers is presented. The previous approach, valid for inertia-free vents, is advanced by appending to it a new model of translating inertial vent cover displacement. The model and CINDY code are validated against experiments by Höchst and Leuckel (J. Loss Prev. Process Ind. 11 (1998) 89) in a 50-m3 vessel with vertically translating covers with surface densities of 42 and 89 kg/m2 at conditions of initially quiescent and turbulent mixtures. It is demonstrated for the first time that modelling of the vent cover jet effect is crucial for prediction of interdependent pressure-time and cover displacement-time transients, whereas air drag force and cushioning effects are negligible. The model was used further to investigate the influence of vent cover surface density on venting generated turbulence, via comparisons with experimental data of Cooper et al. (Combust. Flame 65 (1986) 1) in a 1-m3 enclosure with vertically translating covers of various surface densities up to 200 kg/m2. The increase of the turbulence factor, i.e. total premixed flame front wrinkling factor, with cover inertia is obtained and explained.  相似文献   

16.
Results from cornstarch explosion tests using a flameless venting device (mounted over a burst disc) on an 8 m3 vessel are presented and used to determine the overall efficiency of the device, which is defined as the ratio between its effective vent area and the nominal vent area. Because these devices are comprised of an arrestor element mounted over an impulsively-actuated venting device (such as a burst disc), the functional form of the overall efficiency is taken as the product of the area efficiency (i.e., the ratio between the effective vent area of the entire assembly to that of the venting device without the arrestor element) and the burst efficiency (i.e., the ratio of the effective vent area of the venting device without the arrestor element to the nominal vent area). The effective vent areas are calculated from measured overpressures using three different empirical correlations (FM Global 2001, NFPA 2007, and VDI 2002). Furthermore, due to significant variations in the effective reactivity from test to test, a correction factor proportional to the initial flame speed is applied when determining the area efficiency. In general, it was found that the FM Global and NFPA methodologies yield consistent results with less scatter than VDI 3673.  相似文献   

17.
An investigation into the effects of vent ducts on reduced explosion pressures is described. Experiments were made using an 18.5m3 explosion vessel and a modified 20 1 sphere, with dusts having Kst values ranging from 144 bar ms−1 to 630 bar ms−1. The vent area/vessel volume ratio bursting pressure of the vent cover, and the length to diameter ratio of the vent duct have been varied. Straight vent ducts, and ducts containing sharp 45° and 90° bends have been used.A simple model to describe the effect of vent ducts on the reduced explosion pressure has been derived and compared with the experimental results. Agreement is shown to be satisfactory in nearly all cases. A comparison between the experimental results and guidance on the effect of vent ducts already available in the literature is discussed.  相似文献   

18.
A quantitative risk assessment (QRA) tool has been developed by TNO for the external safety of industrial plants with a dust explosion hazard. As a first step an industrial plant is divided into groups of modules, defined by their size, shape, and constructional properties. Then the relevant explosion scenarios are determined, together with their frequency of occurrence. These include scenarios in which one module participates, as well as domino scenarios. The frequency is partly based on casuistry.

A typical burning velocity is determined depending on the ignition type, the dust properties and the local conditions for flame acceleration. The resulting pressure development is predicted with the ‘thin flame model’. Module failure occurs when the explosion load exceeds thresholds, which are derived from single degree of freedom (SDOF) calculations for various types of modules. A model has been developed to predict the process of pressure venting after module failure and the related motion of launched module parts.

The blast effects of the primary explosion are based on results from calculations with BLAST3D. The blast and flame effects of the secondary external explosion due to venting are calculated using existing models. The throw of fragments and debris is quantified with a recently developed model. This model is based on trajectory calculations and gives the impact densities, velocities, and angles as output. Furthermore the outflow of bulk material is taken into account. The consequences for external objects and human beings are calculated using existing models. Finally the risk contours and the Societal risk (FN curve) are calculated, which can be compared to regulations.  相似文献   


19.
The overpressure peaks and flame propagation characteristics of hydrocarbon fuel-air mixtures vented deflagration in a 20-L cylindrical vessel with a slight static activation overpressure (PST = 2.5 kPa) and five vent opening ratio were studied by a series of experiments. The experiments focused on the effect of vent opening ratio on the overpressure peaks and flame propagation characteristics of hydrocarbon fuel-air mixture vented deflagration. The internal overpressure-time profiles and high-speed photographs of flame propagation processes were obtained. The results showed that three overpressure peaks were distinguished in the internal overpressure-time profiles, caused by the burst vent cover (pburst), the acceleration of burnt gas (pfv), and the fierce external deflagration of vented unburned fuel (pext), respectively. The changing of the vent opening ratio had almost no effect on the value of pburst and (dpburst/dt). With increasing vent opening ratio, the values of pfv, pext, (dpfv/dt) and (dpext/dt) showed a decreasing trend while the values of pburst and (dpburst/dt) were nearly constant. The flame presented a hemispherical shape before the vent cover ruptured then developed as a mushroom shape after accelerated to external field. There were three flame speed peaks during flame propagation process, resulted from venting flow acceleration, external deflagration, and axial heat flux formed by internal combustion. With the increase of vent opening ratio, all of the maximum flame speed, external average flame speed, maximum flame distance and external flame duration showed a downward trend, excepting for the internal average flame speed almost remained constant.  相似文献   

20.
为了研究墨粉在爆炸泄压过程中燃烧与流动的变化机制,通过改变泄爆片尺寸、墨粉浓度以及泄爆片的惯性力等参数对爆炸泄放过程中反应釜中压力以及外场火焰形态变化进行试验研究,同时与完全封闭空间内不同墨粉浓度的压力曲线对比。研究结果表明:相同泄爆开口尺寸下,粉尘浓度与受控爆炸压力(采用爆炸泄压保护措施后工业腔体内产生的压力)负相关;开口尺寸增加可以提升泄压效率;结合外场火焰形态的变化情况揭示声动火焰不稳定性对反应釜中压力发展的影响;通过无惯性泄爆试验的对比证明泄爆片惯性对受控爆炸压力的影响不可忽视。  相似文献   