首页 | 本学科首页   官方微博 | 高级检索  
相似文献
 共查询到20条相似文献,搜索用时 15 毫秒
1.
Explosions caused by the rapid release of energy from the expansion of burnt gases, along with an associated pressure rise, in an enclosure can be mitigated by venting. Many empirical equations have been derived based on vented gas deflagration phenomena. In the present paper, four empirical equations for gas venting were reviewed, i.e., NFPA 68, the European Standard (EN 14994), Molkov et al. and Bradley and Mitcheson in order to assess their reliability and applicability for predicting the reduced explosion pressure (Pred) of propane-air, methane-air and hydrogen-air mixtures at three different chamber-scale volumes. The results showed that the NFPA 68 correlation is the most appropriate method for predicting Pred, while Bradley and Mitcheson gave values closer to those of experimental data for propane-air mixtures in medium and larger chambers, respectively. However, none of the predicted correlations was able to provide a reasonable prediction of Pred in a hydrogen-air explosion. In addition, these predicted correlations showed greater discrepancies in Pred values in the presence of vent area, ignition position and obstacles.  相似文献   

2.
Scaling parameters for vented gas and dust explosions   总被引:3,自引:0,他引:3  
Results of experiments or calculations for vented explosions are usually presented by expressing a term containing the peak (reduced) pressure as a function of a vent parameter. In gas explosions, the reactivity of the system has been typically characterized through an effective burning velocity, uf. In the case of dust explosions, a normalized peak rate of pressure rise, K(=V1/3(dp/dt)max), has been used instead. Depending on the chosen approach, comparisons between systems with the same “reactivity” take different meanings. In fact, correlation formulas resulting from these two approaches imply different scaling between important system parameters. In the case of a constant-uf system, and for sufficiently large vent areas, the reduced pressure, Δpr, is approximately proportional to the square of the peak unvented pressure, Δpm. On the other hand, correlations developed for constant-K systems imply proportionality of Δpr with Δpm raised to a power between −5/3 and −1, with the exact value depending on the assumptions made on the shape of the pressure profile. While the ultimate resolution of the details of the scaling may require recourse to experiments, this theoretical analysis offers a tool for the planning of such experiments and for the interpretation of their results. The paper provides a discussion of these scaling issues with the help of predictions from an isothermal model of vented explosions.  相似文献   

3.
A typical building consists of a number of rooms; often with windows of different size and failure pressure and obstructions in the form of furniture and décor, separated by partition walls with interconnecting doorways. Consequently, the maximum pressure developed in a gas explosion would be dependent upon the individual characteristics of the building. In this research, a large-scale experimental programme has been undertaken at the DNV GL Spadeadam Test Site to determine the effects of vent size and congestion on vented gas explosions. Thirty-eight stoichiometric natural gas/air explosions were carried out in a 182 m3 explosion chamber of L/D = 2 and KA = 1, 2, 4 and 9. Congestion was varied by placing a number of 180 mm diameter polyethylene pipes within the explosion chamber, providing a volume congestion between 0 and 5% and cross-sectional area blockages ranging between 0 and 40%. The series of tests produced peak explosion overpressures of between 70 mbar and 3.7 bar with corresponding maximum flame speeds in the range 35–395 m/s at a distance of 7 m from the ignition point. The experiments demonstrated that it is possible to generate overpressures greater than 200 mbar with volume blockages of as little as 0.57%, if there is not sufficient outflow through the inadvertent venting process. The size and failure pressure of potential vent openings, and the degree of congestion within a building, are key factors in whether or not a building will sustain structural damage following a gas explosion. Given that the average volume blockage in a room in a UK inhabited building is in the order of 17%, it is clear that without the use of large windows of low failure pressure, buildings will continue to be susceptible to significant structural damage during an accidental gas explosion.  相似文献   

4.
为了研究障碍物对油气泄压爆炸火焰传播特性的影响规律,进行了不同数量障碍物工况下的对比实验,并利用纹影仪和高速摄影仪记录了火焰传播过程,针对障碍物对火焰形态、火焰锋面位置及火焰传播速度的影响规律进行了研究,结果表明:圆柱体障碍物会导致油气泄压爆炸火焰形态产生褶皱和弯曲变形,诱导层流火焰向湍流火焰转变,加速火焰的传播,对油气泄压爆炸火焰的初始传播形态有显著影响;随着障碍物数量的增多,火焰锋面传播距离点火端的最大距离增大,但到达最远距离的时间减少;障碍物能够增强火焰的传播速度,尤其对障碍物下游火焰影响最为显著,随着障碍物数量的增多,火焰传播的最大速度也随之增大,但达到最大火焰传播速度的时间却随之减少;障碍物的存在增大了油气泄压爆炸过程外部爆炸压力,并且随着障碍物数量的增多,外部爆炸压力峰值增长幅度增大。  相似文献   

5.
A three-dimensional gasdynamic model with constant burning rate is applied for the prediction of the maximum pressure rise from gaseous combustion in vented enclosures. A series of calculations for an enclosure with aspect ratio close to unity are presented. Both cases with and without obstacles in the enclosure are considered. Results of calculations are compared with a simple 0D solution for spherical vessels. It is shown that, in cases without obstacles, the 0D solution for the maximum reduced overpressures is close to the predictions of the detailed modeling. In cases with obstacles, the detailed simulation gives significantly higher overpressures than those from the 0D model. However, in all the cases the reduced pressures are correlated well with the maximum flame surface area.  相似文献   

6.
A pilot scale interconnected vessels experiment system was established, and the closed and vented gas explosion characteristics in the system were studied, using 10% methane–air mixture. Regularity of pressure variation in vessels and flame propagation in linked pipes was analyzed. Furthermore, the effects of transmission style, ignition position, pipe length, and initial pressure on explosion severity were discussed. For the closed explosion: explosion in interconnected vessels presents strongly destructive power to secondary vessel, especially transmission from the big vessel to the small one; the worst ignition position is shifting from ignition in the interconnected pipe to the walls of the two vessels; as far as ignition in big vessel is concerned, the peak pressure in secondary vessel increases with the pipe length much faster than that for ignition in small vessel; the peak pressures in two vessels are approximate linear functions of initial pressure. For the vented explosion: the transmission style and interconnected pipe length have significant impacts on the effect of venting on the protection; in order to obtain the better venting effect, the use of a divergent interconnected pipe from the big vessel to the small one in industry is advised and it is necessary to reduce the interconnected pipe length as far as possible or install flame arrester in the interconnected pipe.  相似文献   

7.
A study on the obstacle-induced variation of the gas explosion characteristics   总被引:13,自引:0,他引:13  
A study on the variation of the gas explosion characteristics caused by the built-in obstacles was conducted in enclosed/vented gas explosion vessels. It has been well known that the obstacles in pipes and long ducts would accelerate the flame propagation, and cause the transition from deflagration to detonation. In this study, the explosion characteristics and the flame behavior of vented explosions and constant-volume explosions were investigated. Experiments were carried out in a 270-liter and 36-liter hexahedron vessels filled with LPG–air mixture. The explosion characteristics of the gas mixture were determined by using a strain-responding pressure transducer. The flame behavior was recorded by using a high-speed video camera. The shape and the size of the obstacle, and the gas concentration, were adjusted in the experiments.

It can be seen from the experimental results that, instead of being accelerated, the flame propagation inside the explosion vessel is decelerated by the plate obstacles fixed at the bottom of the vessel. Also, the characteristics of the enclosed explosion are not so affected by the built-in obstacles as those of the vented explosion are. It is believed that the eddy-induced turbulence behind the obstacle decelerates the flame propagation.  相似文献   


8.
This paper analyses the experimental data reported by Höchst and Leuckel (1998) for combustion in partially confined vessels and uses the data from these experiments to establish the burning rate based on a simplified model for the combustion process in such vessels. The model establishes three fundamental parameters which are necessary in characterizing the combustion process. These are: i) the burning rate, ii) the fraction of vent area occupied by burnt gas (or discharge sub-model), and iii) the vent area model (if cover mechanisms with variable vent areas are utilized). A set of independent equations is derived to determine the burning rate according to conservation of mass and volume for each gas fraction separately along with a general equation based on general volume conservation. Using this method we are able to describe the combustion process and examine the effect of various discharge models. The advantages of the model presented here include rapid applicability and a valuable analysis to derive mass burn rate and other useful parameters using experimental data from vented explosions with reasonable residual reactant values. Based on these results, the correct interpretation of the obtained burning rate can be used in order to explain the correct prediction of flame velocity and position according to a reasonable discharge model. The paper also evaluates the suitability of several discharge models for phenomenological models of vented explosions. The most appropriate is a Heaviside step function which considers that only unburnt gas is initially expelled, with that component decreasing and the burnt gas component increasing until finally only burnt gas is expelled. The obtained results in this study can be used to predict the burning rate behavior and the combustion process of similar problems.  相似文献   

9.
液化石油气爆炸范围及爆炸力的测定   总被引:1,自引:0,他引:1  
液化石油气、瓦斯等可燃气体的爆炸防治是一个非常迫切需要解决的问题.利用自制可燃气体爆炸箱来模拟可燃气体爆炸,并通过光干涉甲烷测定仪来测定混合气体爆炸时的甲烷百分含量,再推算出液化石油气的爆炸范围和计算爆炸力.  相似文献   

10.
Coal mine refuge chambers are new devices for coal mine safety which can provide basic survival conditions after gas explosion. In order to simulate the propagation of underground methane/air mixture blast wave, and check structural safety of coal mine mobile refuge chamber, an underground tunnel model and a refuge chamber model have been established based on explicit nonlinear dynamic ANSYS/LS-DYNA 970 program. Results show that the reflected wave pressure on the impact surface was about two times higher than that on the incident one. The relationship between the pressure fields of the chamber was analyzed. The maximum pressure of gas explosion reached about 0.71 MPa, and the pulse width was 360 ms. The maximum absolute displacement and stress occurs at the main door center and the connection of stiffeners and the front plate, respectively. The entire coal mine mobile refuge chamber was in elastic state and its strength and stiffness meet the safety requirements. The cabin door, the front plate and the connecting flange at cabin back as well as the stiffeners on each side were the most critical components. Suggestions were put forward for the refuge chamber.  相似文献   

11.
Gas explosion in connected vessels usually leads to high pressure and high rate of pressure increase which the vessels and pipes can not tolerate. Severe human casualties and property losses may occur due to the variation characteristics of gas explosion pressure in connected vessels. To determine gas explosion strength, an experimental testing system for methane and air mixture explosion in a single vessel, in a single vessel connected a pipe and in connected vessels has been set up. The experiment apparatus consisted of two spherical vessels of 350 mm and 600 mm in diameter, three connecting pipes of 89 mm in diameter and 6 m in length. First, the results of gas explosion pressure in a single vessel and connected vessels were compared and analyzed. And then the development of gas explosion, its changing characteristics and relevant influencing factors were analyzed. When gas explosion occurs in a single vessel, the maximum explosion pressure and pressure growth rate with ignition at the center of a spherical vessel are higher than those with ignition on the inner-wall of the vessel. In conclusion, besides ignition source on the inner wall, the ignition source at the center of the vessels must be avoided to reduce the damage level. When the gas mixture is ignited in the large vessel, the maximum explosion pressure and explosion pressure rising rate in the small vessel raise. And the maximum explosion pressure and pressure rising rate in connected vessels are higher than those in the single containment vessel. So whenever possible, some isolation techniques, such as fast-acting valves, rotary valves, etc., might be applied to reduce explosion strength in the integrated system. However, when the gas mixture is ignited in the small vessel, the maximum explosion pressures in the large vessel and in the small vessel both decrease. Moreover, the explosion pressure is lower than that in the single vessel. When gas explosion happens in a single vessel connected to a pipe, the maximum explosion pressure occurs at the end of the pipe if the gas mixture is ignited in the spherical vessel. Therefore, installing a pipe into the system can reduce the maximum explosion pressure, but it also causes the explosion pressure growth rate to increase.  相似文献   

12.
Simulations of gas explosion of hydrogen/air mixture inside two rooms connected by ducts are carried out. Scalar transport chemical reaction model and LES turbulence model are utilized to reduce the calculation load and to conduct real-scale analysis. The effects of ignition source locations and volume of ignited room are analyzed, and the time history of pressure and rate of pressure rise in each room are focused in this study. When the volume of the ignited room is larger than the other room, the high pressure from the other room causes a force to act on the partition to the ignited room. This study indicates that the current technique can predict specific features of gas explosions inside two rooms connected by the ducts.  相似文献   

13.
路长  王小康  刘洋  王鸿波 《火灾科学》2018,27(3):174-180
为实现主动抑制瓦斯爆炸,研制了高速抑爆响应系统。选用尺寸为150mm×150mm×1 600mm的有机玻璃管道,在CH4体积分数为9.5%的条件下进行响应系统测试实验。系统采用火焰传感器进行爆炸火焰探测,通过所设计的程序自主判定瓦斯爆炸的发生并输出控制电信号,以继电器或MOS管为电路控制开关,通过电磁阀控制抑爆剂的喷出。实验结果表明,火焰传感器探测、信号采集、爆炸判断、输出电信号的总平均耗时为22ms,抑爆剂开始释放的平均时刻为59.8ms,抑爆剂释放到管道顶端的平均时刻为79.8ms。而爆炸火焰传播到达喷头所在1.0m处平均时刻为176.2ms。实验表明该系统具有高速主动抑爆响应功能和良好的稳定性、可靠性。  相似文献   

14.
针对瓦斯爆炸事故在矿井开采中的危害及防治,从爆炸发展规律和爆炸防治两大方面对国内外瓦斯爆炸研究状况进行了综合评述.国内外学者通过理论法、实验法、数值模拟法对瓦斯爆炸进行研究,瓦斯爆炸发展规律方面的研究涉及到瓦斯爆炸的机理、瓦斯组分及浓度对爆炸发展规律的影响、爆炸发生的条件及危害、爆炸过程中的燃烧阶段变化及流体流动状态变...  相似文献   

15.
Gas explosion is one of the main disasters in coal mining. Plenty of coal gangue are generally distributed in the disaster areas in gob. Experiments were carried out to explore the propagation law of the gas explosion distributed by coal gangue. The variation characteristics of the overpressure, pressure rise rate, and flame shape with void fractions were analyzed. The results showed that the effect of the coal gangue on the explosion intensity changed from suppression to acceleration with the increase of void fraction, the flame front upstream blockage area changed from laminar state to turbulent divergent state, and a reverse flame was formed. When the void fraction of the coal gangue was 0.50–0.65, the maximum overpressure downstream of the blocked area were positively correlated with the void fraction and the critical suppression range was between 0.50 and 0.55. When the void fraction was lower than 0.50, the flame was quenched in the coal gangue, neither the flame nor the pressure could pass through the blocked area. It is helpful to guide the improvement of coal recovery process to avoid the expansion of the explosion impact in coalmine gob.  相似文献   

16.
In this study, in order to research the synergistic inhibition effect of nitrogen and ultrafine water mist on gas explosion in a vented duct, a semi-confined transparent chamber was designed with the size of 120 × 120 × 840 mm, and the experiments were carried out with stoichiometric methane/air premixed mixture (fraction of methane: 9.5%), adding different fractions of nitrogen and ultrafine water mist. The experimental results showed the following: The combination of nitrogen and ultrafine water mist had a synergistic inhibiting effect on methane/air explosion, which was preferable to the single use of any kind. With the increase of spraying time of water mist and fraction of nitrogen, the initial shape of the explosion flame became snakelike, and at the same time the peak flame propagation speed and peak overpressure decreased significantly. When the nitrogen fraction was increased to 10% and the mist spraying time was increased to 2min, synergistic inhibiting effect on overpressure was high efficient. However, with the increase of spraying time of water mist and fraction of nitrogen going on, the amount of increase of explosion inhibition efficiency was gradually reduced.  相似文献   

17.
The coupling of gas explosion flame and shock wave is analyzed. In the gas explosion process, shock wave is affected by the flame directly, and shock wave also induces the flame. Inhibiting explosion can be achieved by the interference between the flame and shock wave propagation. If the coupling effects can be damaged, the adverse effects caused by the explosion should be mitigated and controlled. According to the structure characteristics of foam ceramics, the coupling effects mechanism of ceramic foam on gas explosion flame and shock wave is researched. When the explosion goes through the structure of foam ceramics, the flame can be quenched and the shock wave be attenuated. After the flame is quenched, the supply of precursor shock wave energy is cut off. Due to lack of energy supply, the destructive effects of blast wave will be reduced effectively. Coupling effects of the flame and shock wave can be damaged by the special structure of foam ceramics. Studies suggest that a certain function to represent the structure characteristics of foam ceramics must exist. For a certain material of foam ceramics, the sure porosity δ and the pore diameter d also can be get, which is the key to research and develop foam ceramic suppression technology of gas explosion.  相似文献   

18.
Vacuum chamber is a new method to suppress the gas explosion. The explosion propagation characteristics have been studied in an L-shaped channel (tubes joined a right angle) with a vacuum chamber in the region of joining of the tubes. The vacuum chamber separated from the inner tubular space with the help of a diaphragm pierced by firing pin. The results demonstrate that the effect of explosion suppression of vacuum chamber is related to the break-up time of diaphragm and the position of the explosive flame front. When the diaphragm breaks up, the shorter the distance of flame front propagation is, the closer the flame front gets to the vacuum chamber, and the better effect of explosion suppression is, conversely, the worse the effect of explosion suppression is.  相似文献   

19.
20.
To study the mechanism of the suppressing effect of Expanded Aluminium (EA) on the premixed gas explosion, premixed methane-air and propane-air gases were undergone explosion reaction in the presence of EA in a self-designed closed pipeline with the overpressures and the compositions, rates and sensitivities of products analyzed. The results showed that the 9.5% methane-air and 5% propane-air explosions produced peak pressures decreased by 79.3% and 65.6%, and residual methane and propane contents increased by 270% and 560% respectively than without EA. In addition, the results revealed that the explosions of propane in the presence of EA produced less methane and carbon oxides contents, but more ethylene and propylene contents. The simulation showed that H, O, and OH are the key factors affecting the rate of products. The product compositions, together with other parameters, suggested that EA decreased temperature, inhibited chain initiation and propagation reaction, but facilitated chain termination reaction by advancing and accelerating the gas phase and wall destruction reaction of radicals, especially collisions and concentration of key free radicals. This new research method based on the analysis of explosion products can be used for in-depth research into gas explosion features and shed light on the suppressing mechanism of EA in flammable gas explosion.  相似文献   

设为首页 | 免责声明 | 关于勤云 | 加入收藏