Large cooking oil pool fires, occurring in industrial oil cookers, present a severe hazard to food processing plants due to their size and the large amount of hot oil involved. This paper reports a series of full-scale fire experiments conducted in a large industrial oil cooker mock-up. The characteristics of large cooking oil pool fires and the effect of oil depth and hood position in the oil cooker on fire growth were studied. The use of water mist for extinguishing large oil pool fires and their extinguishing performance under different discharge pressure and with different types of water mist systems were investigated. Experimental results showed that the cooking oil underwent a substantial expansion in volume during heating. The fires developed quickly once the oil auto-ignited. The fire growth rate was affected by the oil depth in the pan and the hood position in the oil cooker. The water mist fire suppression systems effectively extinguished large cooking oil fires and prevented them from re-igniting. Their extinguishing performance was determined by the type of water mist system, discharge pressure and hood position in the oil cooker. 相似文献
This paper presents detailed data on the thermal response of two 500 gal ASME code propane tanks that were 25% engulfed in a hydrocarbon fire. These tests were done as part of an overall test programme to study thermal protection systems for propane-filled railway tank-cars.
The fire was generated using an array of 25 liquid propane-fuelled burners. This provided a luminous fire that engulfed 25% of the tank surface on one side. The intent of these tests was to model a severe partially engulfing fire situation.
The paper presents data on the tank wall and lading temperatures and tank internal pressure. In the first test the wind reduced the fire heating and resulted in a late failure of the tank at 46 min. This tank failed catastrophically with a powerful boiling liquid expanding vapour explosion (BLEVE). In the other test, the fire heating was very severe and steady and this tank failed very quickly in 8 min as a finite rupture with massive two-phase jet release. The reasons for these different outcomes are discussed. The different failures provide a range of realistic outcomes for the subject tank and fire condition. 相似文献
After Bhopal disaster, emergency planning in an industrial area has become inevitable. The off-site emergency plan is an integral part of any major hazard control system. Boiling Liquid Expanding Vapour Explosion (BLEVE) leads to fatal consequences. This paper highlights some salient features of the emergency scenario, which ultimately leads to fireball with enormous pressure wave all around. 相似文献
This paper describes the results from a series of fire tests that were carried out to measure the effect of defects in thermal protection systems on fire engulfed propane pressure vessels.
In North America thermal protection is used to protect dangerous goods rail tank-cars from accidental fire impingement. They are designed so that a tank-car will not rupture for 100 min in a defined engulfing fire, or 30 min in a defined torching fire. One common system includes a 13 mm blanket of high-temperature ceramic fibre thermal insulation covered with a 3 mm steel jacket. Recent inspections have shown that some tanks have significant defects in these thermal protection systems. This work was done to establish what levels of defect are acceptable from a safety standpoint.
The tests were conducted using 1890 l (500 US gallon) ASME code propane pressure vessels (commonly called tanks in the propane industry). The defects tested covered 8% and 15% of the tank surface. The tanks were 25% engulfed in a fire that simulated a hydrocarbon pool fire with an effective blackbody temperature of 870 °C.
The fire testing showed that even relatively small defects can result in tank rupture if the defect area is engulfed in a severe fire, and the defect area is not wetted by liquid from the inside. A wall failure prediction technique based on uniaxial high-temperature stress rupture test data has been developed and agrees well with the observed failure times. 相似文献
AbstractIn many studies, ergonomics has been shown to influence human performance. The aim of this paper was to demonstrate imp ortan t ergonomics influences on quality in industrial production, from the perspective of interactions between humans, technology, organization, and work environment. A second aim was to elab orate on the implications of these findings for the development of quality management strategies. This paper shows that ergonomics problems in terms of adverse work environmental conditions, in appropriate design of technology, and an unsuitable org an izatio n are important causes of quality deficiencies. Problem solving aimed at improving ergonomics, quality, and productivity simultaneously is likely to obtain sup po rt from most of the interest parties of the company, and may also enhance participation. Ergonomics has the potential of becoming a driving force for the development of new quality management strategies. 相似文献
AbstractThe participative standard with feedback condition was superior to the assigned difficult (140% of normal) standard with feedback condition in terms of worker productivity. The percentage increase in worker productivity with the participative standard and feedback condition was 46%, whereas the increase in the assigned difficult standard with feedback was 23%, compared to the control group (no standard, no feedback). Worker productivity also Improved significantly as a result of assigning a normal (100%) production standard with feedback, compared to the control group, and the increase was 12%. The participative standard with feedback condition emerges as the optimum strategy for improving worker productivity in a repetitive industrial production task. 相似文献
The purpose of this study was to develop a model for an integrated estimation of the functional state of the human organism (FSHO) and an integral estimation of physical factors (PF) for hygienic rating. Tests were performed twice with 3 men in 0.7-clo clothing during 4-hr mental work with 9 combinations of 4 PF: wideband noise (55–83 dB(A)), whole-body vibration (6 Hz, az = 0.2–1.8 ms?2), air temperature (18–30 °C), and illumination (1, 3, 5 lx). Thermoregulatory, cardiovascular, and psychophysiological reactions and temporary threshold of hearing (TTS2) shifts were studied. For the integral estimation of PF influence on FSHO the model F(y1, y2, ... ym) = f(x1, x2, ... xn) was used, relating both FSHO and PF sets. The most important physiological parameters in creating FSHO are defined and the contribution of individual parameters of FSHO and PF is found. 相似文献