This paper presents detailed data on the thermal response of two 500 gal ASME code propane tanks that were 25% engulfed in a hydrocarbon fire. These tests were done as part of an overall test programme to study thermal protection systems for propane-filled railway tank-cars.
The fire was generated using an array of 25 liquid propane-fuelled burners. This provided a luminous fire that engulfed 25% of the tank surface on one side. The intent of these tests was to model a severe partially engulfing fire situation.
The paper presents data on the tank wall and lading temperatures and tank internal pressure. In the first test the wind reduced the fire heating and resulted in a late failure of the tank at 46 min. This tank failed catastrophically with a powerful boiling liquid expanding vapour explosion (BLEVE). In the other test, the fire heating was very severe and steady and this tank failed very quickly in 8 min as a finite rupture with massive two-phase jet release. The reasons for these different outcomes are discussed. The different failures provide a range of realistic outcomes for the subject tank and fire condition. 相似文献
The present study focuses on the definition and assessment of overpressure threshold values for the damage to equipment caused by blast waves originated by primary accidental scenarios. A revision of literature data and of the available damage probability models was carried out. Threshold values were proposed for different categories of process equipment, taking into account either damage levels or release intensities following the loss of containment. Specific threshold values for domino effect were also proposed. 相似文献
In our today's societies, many dangerous chemicals are produced and transported. Due to the vast use of chemicals, more chemical accidents are taking place with huge losses. In this study a city hazardous gas monitoring network was designed to detect the dispersion of toxic and combustible gases in the primary stages. The network could cover hazardous chemical facilities, important hazardous chemical routes, warehouses and special locations which may be the targets of terrorist attacks. The network is consisted of several local networks and a central control panel complex. Each local network has a local control panel in the center and many detectors and sounders around it at distances less than 3000 m that communicate with the local control panels wirelessly. In each location there are two types of gas detectors, toxic and combustible, and a sounder which are equipped with a wireless, radio frequency modem allowing the units to communicate readings and other information on a real-time basis with a remotely located local control panel. High sensitive Photo Ionization Detectors, PIDs, are used to provide fast and low-level on-site screening for chemicals contamination. Combustible gas detectors are the second choice to sense the combustible gas and verify the readings of PIDs in this regard. The central panel consists of several connected control panels work uniquely helping a computer set and the appropriate software and communicate with local control panels via telephone lines. All of the network components are shown on the monitor of central panel with special symbols by geographical information system program. The system is fully addressable so that the high level detection of a detector produces a blinking color double-circle around its symbol in GIS plan. In case of high level gas detection, a team of experts who are fully equipped with different portable detectors depart to the site to test the field to identify the chemicals. All readings of detectors are saved in a data bank and then analyzed to find any chemicals spills and leakages. The network was simulated by a special program so that the components of local networks and the central panel are shown in separate windows. By clicking on one detector on environmental window the formerly designed responses will be activated in central panel window. 相似文献