Abstract:A multistaged combustion burner designed for in-furnace NOx control and high combustion efficiency is being evaluated for high nitrogen content fuel and waste incineration application in a 0.6 MW package boiler simulator. A low NOx precombustion chamber burner has been reduced in size by approximately a factor of two (from 600 to 250 ms first-stage residence time) and coupled with (1) air staging, resulting in a three-stage configuration, and (2) natural gas fuel staging, yielding up to four stolchlometric zones. Natural gas, doped with ammonia to yield a 5.8 percent fuel nitrogen content, and distillate fuel oil, doped with pyridine to yield a 2 percent fuel nitrogen content, were used to simulate high nitrogen content fuel/waste mixtures. The multistaged burner reduced NO emissions by 85 percent from emission levels from a conventional unstaged burner mounted on a commercial package bollerTA minimum NO emission level of 110 ppm was achieved in the fuel oil tests, from a level of 765 ppm for conventional firing. This is compared with a 160 ppm minimum NO level achieved in gaseous fuel tests, from an uncontrolled level of 1000 ppm. Boiler fuel staging, or reburnlng, appears to be superior to air staging for high combustion efficiency due to its minimal fuel-rich core and second flame front in the boiler.