Air intake contamination by building exhausts: tracer gas investigation of atmospheric dispersion models in the urban environment
Authors:Lazure Louis  Saathoff Pat  Stathopoulos Ted
Institution:Institut de Recherche Robert-Sauvé en Santé et en Sécurité du Travail, Montréal, Québec, Canada.
Abstract:The establishment of a safe distance between sources of pollution and air intakes is based on a complex exercise that should take into account several wind, physical, and topographical factors. To estimate the maximum concentrations of the pollutants as a function of the distance from the emission source, some heating, ventilation, and air conditioning (HVAC) system designers use the atmospheric dispersion models suggested by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). Two of these models, the Halitsky and Wilson-Chui-Lamb models, have been developed and evaluated mainly with laboratory data. There have been relatively few evaluations with full-scale field data. The objective of this study, carried out on a building in downtown Montreal, Quebec, Canada, was to compare the measured concentrations of a tracer gas emitted by an exhaust stack with those predicted by these models. The results indicate that the Halitsky model gives lower than actual dilution, while the Wilson-Chui-Lamb model generally gives acceptable estimates, with occasional over-estimations of the dilution.
Keywords:
本文献已被 PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏