750kV罐式断路器内部接地故障保护动作行为分析
引用本文:陈海军.750kV罐式断路器内部接地故障保护动作行为分析[J].防灾减灾工程学报,2012(1):42-44.
作者姓名:陈海军
作者单位:宁夏电力公司超高压分公司,宁夏银川 750011
摘    要:针对一起750kV罐式断路器内部接地故障,通过对保护动作数据和波形图进行综合分析,快速、准确地找出故障点并排除了故障。分析结果表明:故障原因为拉杆绝缘材料存在质量问题,在稳态电压下内部放电,致使其绝缘击穿。

关 键 词:750  kV罐式断路器  单相接地  绝缘击穿

Course analysis on an inside grounding fault leading protection device action of 750 kV tank breaker
Chen Haijun.Course analysis on an inside grounding fault leading protection device action of 750 kV tank breaker[J].Journal of Disaster Prevent and Mitigation Eng,2012(1):42-44.
Authors:Chen Haijun
Institution:EHV Filiale of Ningxia Electric Power Company, Yinchuan Ningxia 750011 , China
Abstract:Aiming at an inside grounding fault of 750 kV tank breaker, analyzes the action data andwaveshape chart of protection device, finds out fault spot and eliminates the fault. The result shows thatthe cause of fault is the insulated material of pull -stick existing quality problem, inside dischargesunder the steady state voltage, brings about its insulated element breakdown.