首页 | 本学科首页   官方微博 | 高级检索  
     

一次回风空调系统PM2.5污染控制策略
引用本文:吕晓慧, 张泠, 刘忠兵, 徐秀. 一次回风空调系统PM2.5污染控制策略[J]. 环境工程学报, 2016, 10(12): 7141-7146. doi: 10.12030/j.cjee.201508012
作者姓名:吕晓慧  张泠  刘忠兵  徐秀
作者单位:1.湖南大学土木工程学院, 长沙 410082
基金项目:国家自然科学基金资助项目(51578221)
摘    要:基于浓度守恒原理建立了一次回风空调系统室内PM2.5浓度模型,研究了过滤器分别安装在新风段、回风段和送风段时过滤效率和新风量的变化对室内PM2.5浓度的影响。模拟结果表明:在室外PM2.5浓度大于室内初始值的条件下,过滤器安装在送风段或回风段时,减少新风有利于室内PM2.5污染控制,过滤器安装在新风段时,根据过滤器效率调节新风,过滤效率小于临界效率,减小新风有利于室内污染控制;在室外PM2.5浓度小于室内初始值的条件下,过滤器安装在送风段或新风段时,增加新风有利于室内PM2.5污染控制,过滤器安装在回风段时,也存在临界效率,过滤效率小于临界值,增加新风有利于室内PM2.5污染控制。

关 键 词:室内空气品质   中央空调   PM2.5   新风稀释   空气过滤
收稿时间:2015-12-01

Primary return air system PM2.5 control strategy
LYU Xiaohui, ZHANG Ling, LIU Zhongbing, XU Xiu. Primary return air system PM2.5 control strategy[J]. Chinese Journal of Environmental Engineering, 2016, 10(12): 7141-7146. doi: 10.12030/j.cjee.201508012
Authors:LYU Xiaohui  ZHANG Ling  LIU Zhongbing  XU Xiu
Affiliation:1.School of Civil Engineering, Hunan University, Changsha 410082, China
Abstract:An indoor PM2.5 concentration model of a primary return air system is presented based on a balance of concentration. The variation in filter efficiency and outdoor air rate on indoor PM2.5 concentration is discussed, with filters installed outdoors at the return and supply vents. The simulation results show that if the outdoor PM2.5 concentration is higher than the initial indoor value, it is recommended to reduce the amount of outdoor air when filter was installed at the supply or return vent to control the indoor PM2.5 concentration. In addition, when a filter was installed for the outdoor airstream, the outdoor air rate had to be adjusted according to the filer efficiency, such as decreasing the outdoor air rate if the efficiency was greater than the critical value. If the outdoor PM2.5 concentration was lower than the initial indoor value, it was recommended to increase the amount of outdoor air when a filter was installed at the supply or outdoor vents. When a filter was installed at the indoor vent, it was advised to increase the outdoor air rate if the efficiency was lower than the critical value.
Keywords:indoor air quality  central air condition  PM2.5  ventilation  air filter
本文献已被 CNKI 等数据库收录!
点击此处可从《环境工程学报》浏览原始摘要信息
点击此处可从《环境工程学报》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏