首页 | 本学科首页   官方微博 | 高级检索  
     检索      


A comparative environmental life-cycle analysis for removing phosphorus from wastewater: biological versus physical/ chemical processes
Authors:Coats Erik R  Watkins David L  Kranenburg Dan
Institution:Department of Civil Engineering, University of Idaho, Moscow, Idaho 83844-1022, USA. ecoats@uidaho.edu
Abstract:Phosphorus can be removed from wastewater biologically, chemically, or through a combination of the two. In this study, we applied environmental life-cycle assessment to develop a metric with which decision-makers can compare processes. Two phosphorus-removal scenarios were contrasted-one based on a desktop-level design and one based on full-scale operational data. To achieve 0.5 mg/L effluent phosphorus (desktop design), a biological-only process would incur 5.2% less effect on global warming potential, as contrasted with a chemical-only process. At an effluent quality of 0.1 mg/L (full-scale facilities), where a biological process augmented with chemicals was contrasted with a chemical-only process, the relative gap increases to 13.2%. As chemical usage increased, the adverse environmental effect of chemical treatment only increased. The results of this study suggest that best practices would center phosphorus removal first on the biological process, with chemical processes added only as necessary.
Keywords:
本文献已被 PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏