An in-situ method of identifying ingredients of zeotropic refrigerants by inversion problem technique
Authors:Ji Zhang  Han Yuan  Yan Li  Hongyu Si  Peichun Cao
Affiliation:1. Marine Engineering, Department of Mechanical Engineering, College of Engineering, Ocean University of China, Qingdao, China;2. Energy Institute, Qilu University of Technology (Shandong Academy of Sciences), Jinan, China;3. Qingdao Hisense Hitachi air conditioning Co Ltd, Qingdao, China
Abstract:An inversion method is applied to identify ingredients of zeotropic refrigerants in a circular duct. In the case of low Reynolds number and constant fluid pressure, the temperature distribution of direct heat transfer problem can be solved numerically. The thermophysical parameters of zeotropic refrigerants are determined by using inversion problem technique, the ingredients of refrigerants can be identified eventually. An in-situ experimental apparatus was proposed and three test samples with different composition refrigerants were conducted in this study. The experiment results show that the relative error of ingredients identification can be limited within 8.33%.
Keywords:Zeotropic refrigerant  thermophysical parameters  ingredient identification  circulation composition  inversion problem technique