首页 | 本学科首页   官方微博 | 高级检索  
     检索      


The performance of solar powered desiccant dehumidifier in India: an experimental investigation
Abstract:The regeneration and adsorption of desiccant wheel for producing the dry air was experimentally investigated. The air needed for regeneration was heated in an evacuated tube solar collector with surface area 4.44 m2. The desiccant wheel is regenerated at the temperature in the range of 43.9–72.6°C. The regeneration and adsorption performances are affected by the regeneration temperature, wheel rotation, air flow rate (process and regeneration) and ambient conditions. By comparing the adsorption and regeneration performance at different air flow rate and constant rph, it was found that maximum adsorption and regeneration rates are obtained at air flow rate of 210.789 kg/h. Regeneration temperature directly affects the effectiveness of the desiccant wheel. Maximum desiccant wheel effectiveness of regeneration sector and adsorption sector is obtained at air flow rate of 105.394 kg/h. The regeneration performance of desiccant wheel with evacuated tube solar air collector is suitable for the Indian climate.
Keywords:evacuated tube solar air collector  desiccant wheel  air flow rate  regeneration  adsorption