首页 | 本学科首页   官方微博 | 高级检索  
     

狭长空间建筑内细水雾幕对顶棚射流火焰抑制效果试验研究*
引用本文:钟委,刘磊,郭超杰,梁天水. 狭长空间建筑内细水雾幕对顶棚射流火焰抑制效果试验研究*[J]. 中国安全生产科学技术, 2022, 18(9): 167-173. DOI: 10.11731/j.issn.1673-193x.2022.09.024
作者姓名:钟委  刘磊  郭超杰  梁天水
作者单位:(郑州大学 力学与安全工程学院,河南 郑州 450001)
基金项目:* 基金项目: 国家自然科学基金项目(51874258)
摘    要:为研究狭长空间内细水雾幕对顶棚射流火焰的抑制效果,通过全尺寸试验研究不同工作压力对射流火焰蔓延形态、雾幕隔热效果及烟气沉降的影响。研究结果表明:随着工作压力的增加,雾滴的动量随之增大,雾幕对射流火焰的扰动作用增强,强化雾幕对射流火焰的阻挡效果;同时,雾幕的隔热效率有明显改善,2.5 MPa时的细水雾幕的隔热效率可达0.75。然而,过大的工作压力会造成烟气层的沉降,工作压力大于2.0 MPa时保护区内烟气层高度低于1.8 m。因此,应综合考虑细水雾幕对射流火焰和烟气的作用,选择适当的工作压力。

关 键 词:细水雾幕  顶棚射流火焰  工作压力  隔热效率

Experimental study on effect of water mist curtain on suppression of ceiling jet flame in long and narrow space buildings
ZHONG Wei,LIU Lei,GUO Chaojie,LIANG Tianshui. Experimental study on effect of water mist curtain on suppression of ceiling jet flame in long and narrow space buildings[J]. Journal of Safety Science and Technology, 2022, 18(9): 167-173. DOI: 10.11731/j.issn.1673-193x.2022.09.024
Authors:ZHONG Wei  LIU Lei  GUO Chaojie  LIANG Tianshui
Affiliation:(School of Mechanics & Safety Engineering,Zhengzhou University,Zhengzhou Henan 450001,China)
Abstract:In order to study the effect of water mist curtain (WMC) on the suppression of ceiling jet flame in the narrow and long space,the influence of different working pressures on the spreading pattern of jet flame,heat insulation effect of mist curtain and smoke deposition was investigated by the full-scale experiments.The results showed that as the working pressure increased,the momentum of droplets increased and the disturbance effect of the mist curtain on the jet flame was enhanced,which strengthened the blocking effect of mist curtain on the jet flame.At the same time,the heat insulation efficiency of the mist curtain improved significantly,and the heat insulation efficiency of WMC at 2.5 MPa could reach 0.75.However,the excessive working pressure would also cause the deposition of smoke layer,and when the working pressure was greater than 2.0 MPa,the height of smoke layer in the protection area was less than 1.8 m.Therefore,the effect of WMC on the jet flame and smoke should be comprehensively considered,and the appropriate working pressure should be selected.
Keywords:water mist curtain   ceiling jet flame   working pressure   heat insulation efficiency
点击此处可从《中国安全生产科学技术》浏览原始摘要信息
点击此处可从《中国安全生产科学技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号