首页 | 本学科首页   官方微博 | 高级检索  
     


Monitoring of Biofilm-associated Legionella pneumophila on Different Substrata in Model Cooling Tower System
Authors:Irfan Türetgen  Aysin Cotuk
Affiliation:(1) Department of Biology, Faculty of Science, Istanbul University, 34118 Vezneciler, Istanbul, Turkey
Abstract:Cooling towers have the potential to develop infectious concentrations of Legionella pneumophila. Legionella counts increases where biofilm and warm water temperatures are present. In this study, biofilm associated L. pneumophila and heterotrophic bacteria were compared in terms of material dependence. Model cooling tower system was experimentally infected by L. pneumophila standard strain and monthly monitored. Different materials were tested for a period of 180 days. The lowest L. pneumophila and heterotrophic plate counts were measured on plastic polymers, whereas L. pneumophila and heterotrophic bacteria were accumulated rapidly on galvanized steel surfaces. It can be concluded that selection of plastic polymers, as a manufacturing material, are suitable for recirculating water systems.
Keywords:Cooling tower   Legionella pneumophila   Legionnaires’   disease  Biofilm  Biofouling
本文献已被 PubMed SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号