首页 | 本学科首页   官方微博 | 高级检索  
     检索      

低压细水雾控制高架仓库实体火灾的实验研究
引用本文:刘宇芳,姚斌,王文伟,舒雅.低压细水雾控制高架仓库实体火灾的实验研究[J].火灾科学,2015,24(3):142-150.
作者姓名:刘宇芳  姚斌  王文伟  舒雅
作者单位:中国科学技术大学火灾科学国家重点实验室,合肥230026;海军蚌埠士官学校兵器系,蚌埠233012;中国科学技术大学火灾科学国家重点实验室,合肥230026;海军蚌埠士官学校兵器系,蚌埠233012;合肥科大立安安全技术股份有限公司,合肥,230088;四川法斯特消防安全性能评估有限公司,成都,610000
摘    要:高架仓库的建筑和储存特点导致其火灾危险性远大于普通仓库,因此高架仓库的消防系统设计研究日益受到重视。目前,高架仓库主要采用的是ESFR自动灭火系统,细水雾灭火系统的应用还较少。通过低压细水雾灭高架仓库实体火灾的实验,记录喷头工作压力、实验点火时间、开始喷水时间、灭火时间及燃烧物的损失量,分析温度、热辐射强度以及喷头流量数据。结果表明:在限定的仓库高度以及货架高度条件下,低压细水雾灭火系统能够有效保护高架仓库,且较其它水喷淋灭火系统用水量少,造成货物的水渍损失小。

关 键 词:高架仓库  低压细水雾  灭火性能  实体火  标准燃烧物
收稿时间:4/3/2015 12:00:00 AM
修稿时间:2015/5/13 0:00:00

Experimental study on low-pressure water mist for protection of high-rack storage
LIU Yufang,YAO Bin,WANG Wenwei and SHU Ya.Experimental study on low-pressure water mist for protection of high-rack storage[J].Fire Safety Science,2015,24(3):142-150.
Authors:LIU Yufang  YAO Bin  WANG Wenwei and SHU Ya
Abstract:Due to special structure traits and storage characteristics, high-rack storage involves higher fire risk compared to ordinary warehouse. Currently, ESFR sprinkler is the primary choice for high-rack storage while water mist is rarely considered. By conducting experiment of low pressure water mist for extinguishing high-rack storage fire, the working pressure of sprinkler, ignition time, spray start time, flame extinction time and the quantity of goods burned were recorded, and the temperature, heat radiation and sprinkler discharge rate were analyzed. The results illustrate that low pressure water mist protects high-rack storage very well under the situation of the limited height of storage and shelf with less water consumption and less water damage compared to other sprinkler systems.
Keywords:High-rack storage  Low-pressure water mist system  Extinguishment characteristic  Practical fire  Standard combustion material
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《火灾科学》浏览原始摘要信息
点击此处可从《火灾科学》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏