首页 | 本学科首页   官方微博 | 高级检索  
     

热障效应对有顶步行街自然排烟的影响
引用本文:张新1,徐志胜1,冉启兵1,2,倪天晓1,2,彭锦志1,2. 热障效应对有顶步行街自然排烟的影响[J]. 中国安全生产科学技术, 2017, 13(1): 28-33. DOI: 10.11731/j.issn.1673-193x.2017.01.005
作者姓名:张新1  徐志胜1  冉启兵1  2  倪天晓1  2  彭锦志1  2
作者单位:1.中南大学 防灾科学与安全技术研究所,湖南 长沙 410075;2. 长沙科锐消防工程技术有限公司,湖南 长沙 410007
摘    要:为了研究热障效应对有顶商业步行街自然排烟的影响,采用理论分析与数值模拟相结合的方法,对不同高度及不同环境温度条件下有顶商业步行街自然排烟时顶棚附近的温度、能见度以及排烟效率进行了分析。结果表明:顶棚附近环境温度越高,自然排烟效果越差,自然排烟效率随顶棚热空气温度的升高呈现线性降低趋势;步行街高度越高,竖直方向的温度差越小,到达顶棚的烟气流速越小,排烟效率越低;当顶棚附近环境温度为45℃时,有顶商业步行街高度不宜超过35 m。

关 键 词:热障效应  有顶商业步行街  自然排烟  能见度  排烟效率

Influence of thermal barrier effect on natural smoke extraction of roofed pedes-trian street
ZHANG Xin1,XU Zhisheng1,RAN Qibing1,2,NI Tianxiao1,2,PENG Jinzhi1,2. Influence of thermal barrier effect on natural smoke extraction of roofed pedes-trian street[J]. Journal of Safety Science and Technology, 2017, 13(1): 28-33. DOI: 10.11731/j.issn.1673-193x.2017.01.005
Authors:ZHANG Xin1  XU Zhisheng1  RAN Qibing1  2  NI Tianxiao1  2  PENG Jinzhi1  2
Affiliation:1. Institute of Disaster Prevention Science and Safety Technology, Central South University, Changsha Hunan 410075, China; 2. Changsha Kerich Fire Protection Engineering Tech. Co. Ltd., Changsha Hunan 410007, China
Abstract:In order to study the influence of thermal barrier effect on natural smoke extraction of commercial roofed pedestrian street, the parameters such as temperature, visibility and smoke extraction efficiency near the roof under the conditions of different heights and environment temperatures were analyzed by using the combined method of theoretical analysis and numerical simulation. The results showed that the higher the environment temperature near the roof, the worse the natural smoke extraction effect, and the natural smoke extraction efficiency presents a linear decrease trend with the increase of hot air temperature at the roof. The higher the height of pedestrian street, the smaller the temperature difference in the vertical direction, the smaller the smoke flow velocity reaching the roof, and the lower the smoke extraction efficiency. The height of commercial roofed pedestrian street should not be more than 35 m when the environment temperature near the roof is 45℃.
Keywords:thermal barrier effect  commercial roofed pedestrian street  natural smoke extraction  visibility  smoke extraction efficiency
本文献已被 CNKI 等数据库收录!
点击此处可从《中国安全生产科学技术》浏览原始摘要信息
点击此处可从《中国安全生产科学技术》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏