灵州换流站换流变压器非电量保护问题分析
引用本文:宋海龙,雷战斐.灵州换流站换流变压器非电量保护问题分析[J].防灾减灾工程学报,2017(5):50-54.
作者姓名:宋海龙  雷战斐
作者单位:国网宁夏电力公司检修公司,宁夏银川 750011
摘    要:针对灵州换流站换流变压器非电量保护所存在影响直流系统运行可靠性的问题,通过对阀侧套管压力继电器一级报警接点、网侧套管升高座瓦斯继电器和阀侧套管末屏电压回路存在问题进行分析,提出相应的改进方案。应用结果表明:改进方案可以快速测定SF。漏气率,使值班运维人员更易于掌控阀侧套管泄漏情况,有利于开展事故应急处置;网侧套管升高座瓦斯继电器由跳闸逻辑改投报警,避免了储油柜油位下降或升高座瓦斯继电器误动作导致直流跳闸的问题,提高了直流系统的运行可靠性。

关 键 词:换流变压器  非电量保护  压力继电器  升高座瓦斯继电器  末屏电压

Non- electric protection analysis of converter transformer in Lingzhou Converter Substation
SONG Hailong,LEI Zhanfei.Non- electric protection analysis of converter transformer in Lingzhou Converter Substation[J].Journal of Disaster Prevent and Mitigation Eng,2017(5):50-54.
Authors:SONG Hailong  LEI Zhanfei
Institution:Maintenance Filiale of State Grid Ningxia Power Co , Y inchuan Ningxia 750011 , China
Abstract:For the problems of non- electric protection of converter transformer affecting thereliability of DC system operation in Lingzhou Converter Substation, analyzes the existing problemssuch as the primary alarm contact of valve side bushing pressure relay without access to theworkstation, the elevated gas relay of net side bushing higher than the lowest position of the oilconservator and the end of the screen voltage circuit of valve side bushing with two- point grounding,puts forward the improvement schemes. The application results show that the improvement schemescan fast determine SF6 leakage gas rate, make the duty operators more liable to master the situation ofthe valve side bushing leakage, which are beneficial to make accident emergent treatment. Theelevated gas relay of net side bushing is changed from trip logic to alarm, avoid DC trip problemresulted from the oil level dropped in oil- storage cabinet or the misoperation of the elevated gas relay,so the scheme improves the reliability of the DC system operation.
Keywords:
点击此处可从《防灾减灾工程学报》浏览原始摘要信息
点击此处可从《防灾减灾工程学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号