The influence of ventilation on indoor/outdoor air contaminants in an office building
Authors:B Berglund  I Johansson  T Lindvall
Abstract:The air quality in a newly built preschool was investigated in a longitudinal study. Typical air contaminants emanating from building materials were determined, their variation over time (0–18 months) was measured, and the influence of the ventilation system (81%–91% recirculation of return air) on contaminant concentrations was studied. Volatile organic compounds were sampled by adsorption on porous polymer, analysed by a GC/FID system, and identified by MS. A spatial build-up in concentration (ppb or μg/m3 levels) is evident for all the organic compounds, as well as for CO2, from the outdoor air, through the ventilation system, and through the rooms to the exhaust air. The longitudinal comparison over time shows that all the organic compounds decline in concentration mainly within the first 6 months of occupancy: 1-butanol 4–14 times, toluene and pentanal + hexanal 2–4 times, while formaldehyde remained at a constant low level of 90 ppb (110 μg/m3). It is difficult to believe that the problems of poor air quality in 100 preschools in Stockholm are caused by the organic compounds alone unless interactions occur. A preschool building needs to be gassed off during the first 6 months after its construction with no recirculation of return air allowed (outdoor air rate approx 4–5 ach). During at least 1–2 additional years, it is desired that the recirculation rate of return air is restricted, perhaps to 50%.