Study of a proposed tunnel evacuation passageway formed by opposite-double air curtain ventilation
Authors:Ran Gao  Angui Li  Wenjun Lei  Yujiao Zhao  Ying Zhang  Baoshun Deng
Institution:1. School of Environmental and Municipal Engineering, Xi’an University of Architecture and Technology, Xi’an, Shaanxi 710055, PR China;2. China Railway First Survey and Design Institute Group Ltd., Xi’an, Shaanxi 710043, PR China
Abstract:Subway tunnel fires often result in catastrophes and heavy casualties. To help people evacuate from a tunnel fire, an opposite-double air curtain ventilation assisted tunnel evacuation system (OTES) is introduced. It can be used to create a safe evacuation passageway that is free of smoke through out the length of the tunnel. The performance of the OTES is compared with that of the traditional ventilation systems: longitudinal ventilation and natural ventilation. The effect of the heat release rate, fire source location, and fire detection time are also discussed.This study also shows that compared with natural ventilation and longitudinal ventilation, the carbon monoxide, CO, concentration with OTES is significantly lower. Given the same HRR, the CO concentration values with OTES are only 0.58–2.41% of natural ventilation or 0.52–3.12% of longitudinal ventilation at the back end of the tunnel. An obviously clear evacuation passageway is created by OTES. The effects of changes in fire source location and fire detection time on tunnel ventilation are tested. Also the effect of these changes on the formation of an evacuation passageway by OTES is reported.
Keywords: