首页 | 本学科首页   官方微博 | 高级检索  
     检索      

成都市某地下空间氡气监测及其防治措施
引用本文:陈弘杰,张庆贤,林意,张建,卢恒,陈瑞,钟经华.成都市某地下空间氡气监测及其防治措施[J].环境工程学报,2021,15(2):650-656.
作者姓名:陈弘杰  张庆贤  林意  张建  卢恒  陈瑞  钟经华
作者单位:成都理工大学核技术与自动化工程学院,地学核技术四川省重点实验室,成都 610059
基金项目:国家重点研发计划;国家自然科学基金
摘    要:地下建筑是城市空间的重要组成部分,氡气是值得关注的地下建筑环境污染物之一。对成都市某地下建筑进行了连续2年的氡浓度监测,通过频数分布和相关性分析了地下建筑氡浓度的季节变化规律以及氡浓度与气温、气压等因素之间的关系。结果表明: 该地下建筑内的氡浓度为8.9~83.1 Bq·m−3,环境氡及其子体所致公众的平均年有效剂量为0.643 mSv,低于《地下建筑氡及其子体控制标准》(GBZ 116-2002)中地下建筑氡浓度限值;氡气浓度呈现明显的季节性变化规律;氡浓度与温度和湿度正相关,与大气压负相关。基于监测数据,建议地下停车场夏季需要加强通风,并在地下停车场开展连续氡浓度监测,根据氡气浓度调节通风设备功率。

关 键 词:地下建筑    室内污染    氡气    监测    通风设备
收稿时间:2019-12-11

Monitoring and prevention and control of radon in an underground building in Chengdu
CHEN Hongjie,ZHANG Qingxian,LIN Yi,ZHANG Jian,LU Heng,CHEN Rui,ZHONG Jinghua.Monitoring and prevention and control of radon in an underground building in Chengdu[J].Techniques and Equipment for Environmental Pollution Control,2021,15(2):650-656.
Authors:CHEN Hongjie  ZHANG Qingxian  LIN Yi  ZHANG Jian  LU Heng  CHEN Rui  ZHONG Jinghua
Institution:Applied Nuclear Techniques in Geosciences Key Laboratory of Sichuan Province, College of Nuclear Technology and Automation Engineering, Chengdu University of Technology, Chengdu 610059, China
Abstract:Underground buildings are an important part of cities and radon is a key air pollutant worthy of attention. This study investigates the seasonal pattern of radon concentration and its relationships with factors such as temperature and atmospheric pressure. This is performed by probability distribution and correlation analysis based on two years’ radon monitoring in an underground parking lot in Chengdu. Results show that the concentration of radon in the underground parking lot is in the range of 8.9 Bq·m-3 and 83.1 Bq·m-3. The public effective dose caused by radon and its progenies is 0.643 mSv, which is below the regulatory limit in the Standard for Controlling Radon and Its Progenies in Underground Space (GBZ 116-2002). The change in radon concentration also shows an evident seasonal pattern. The radon concentration is found to be positively correlated with temperature and humidity and negatively correlated with atmospheric pressure. Based on the measuring data, it is suggested to strengthen ventilation in the underground parking lot in summer. To save energy and ensure public health, continuous radon concentration monitoring can be carried out in the underground parking lot, and the power of ventilation equipment can be adjusted according to the radon concentration.
Keywords:underground buildings  indoor pollution  radon  monitoring  ventilation equipment
本文献已被 万方数据 等数据库收录!
点击此处可从《环境工程学报》浏览原始摘要信息
点击此处可从《环境工程学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号