Abstract:At a MSWI (municipal solid waste incinerator) plant PCDD/PCDF samples (gasphase and particulates) were taken simultaneously be a shock-freezing method in the incinerator combustion chamber at approx. 800°C and in four sampling sections in the boiler at about 490°C, 370°C, 330°C and 270°C. In this way PCDD/PCDF-formation in the flow through the boiler was determined. Two data sets were evaluated. A considerable PCDD/PCDF-formation had occurred already at boiler temperatures of about 490°C; the highest concentration, however, was found at the end of the boiler at about 300°C. The accompanying measuring program of plant parameters made the calculation of the PCDD/PCDF mass flows possible, which allowed the inclusion of the PCDD/PCDF-content in the ESP dust in the mass flow calculations.
Keywords:Waste Incineration  PCDD/PCDF formations  flue gas sampling
本文献已被 ScienceDirect 等数据库收录!