首页 | 本学科首页   官方微博 | 高级检索  
文章检索
  按 检索   检索词:      
出版年份:   被引次数:   他引次数: 提示:输入*表示无穷大
  收费全文   1篇
  免费   0篇
环保管理   1篇
  2023年   1篇
排序方式: 共有1条查询结果,搜索用时 15 毫秒
1
1.
Energy, cost, and environmental concerns play a vital role in understanding governing parameters of distributor design in falling film evaporators. Distributor design is a hidden parameter in many experimental papers. The uniform distribution of liquid refrigerant over the tube bundle mostly depends on two-phase liquid refrigerant and vapor refrigerant. This work conducted experiments with two distribution systems with and without separation of liquid-vapor refrigerant after expansion valve for the same evaporator capacity with R134a as a refrigerant. Results reveal that; separating vapor refrigerant has a positive impact on the approach of the evaporator with an open system distributor arrangement. The highest delta T and lowest practice are found at a heat flux of 13.97 kW/m2 with an available system distributor compared to a closed system with a heat flux of 14.25 kW/m2. The open system arrangement in the distributor is the novel parameter for distributor design, ensuring uniform distribution with minimum pressure drop and dry suction. An open system distributor has an average 16.1% capacity increase over a closed system. The experimental analysis helps to understand different parameters for the design of distributors in falling film evaporators for uniform distribution.  相似文献   
1
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号