The boiling liquid expanding vapour explosion (BLEVE) has existed for a long time and for most of this time it has been cloaked in mystery. Several theories have been put forward to explain this very energetic event but none have been proven. This paper describes a series of tests that have recently been conducted to study this phenomenon.

The study involved ASME code automotive propane tanks with nominal capacities of 400 litres. The tanks were exposed to a combination of pool and/or torch fires. These fire conditions led to thermal ruptures, and in some cases these ruptures resulted in BLEVEs. The variables in the tests were the pressure-relief valve setting, the tank wall thickness, and the fire condition.

In total, 30 tests have been conducted, of which 22 resulted in thermal ruptures. Of those tanks that ruptured, 11 resulted in what we call BLEVEs. In this paper, we have defined a BLEVE as the explosive release of expanding vapour and boiling liquid following a catastrophic tank failure. Non-BLEVEs involved tanks that ruptured but which only resulted in a prolonged jet release.

The objective of this study was to investigate why certain tank ruptures lead to a BLEVE rather than a more benign jet-type release. Data are presented to show how wall temperature, wall thickness, liquid temperature and fill level contribute to the BLEVE process.  相似文献   


2.
On the response of 500 gal propane tanks to a 25% engulfing fire   总被引:1,自引:0,他引:1  
This paper presents detailed data on the thermal response of two 500 gal ASME code propane tanks that were 25% engulfed in a hydrocarbon fire. These tests were done as part of an overall test programme to study thermal protection systems for propane-filled railway tank-cars.

The fire was generated using an array of 25 liquid propane-fuelled burners. This provided a luminous fire that engulfed 25% of the tank surface on one side. The intent of these tests was to model a severe partially engulfing fire situation.

The paper presents data on the tank wall and lading temperatures and tank internal pressure. In the first test the wind reduced the fire heating and resulted in a late failure of the tank at 46 min. This tank failed catastrophically with a powerful boiling liquid expanding vapour explosion (BLEVE). In the other test, the fire heating was very severe and steady and this tank failed very quickly in 8 min as a finite rupture with massive two-phase jet release. The reasons for these different outcomes are discussed. The different failures provide a range of realistic outcomes for the subject tank and fire condition.  相似文献   


3.
This paper describes the results from a series of fire tests that were carried out to measure the effect of defects in thermal protection systems on fire engulfed propane pressure vessels.

In North America thermal protection is used to protect dangerous goods rail tank-cars from accidental fire impingement. They are designed so that a tank-car will not rupture for 100 min in a defined engulfing fire, or 30 min in a defined torching fire. One common system includes a 13 mm blanket of high-temperature ceramic fibre thermal insulation covered with a 3 mm steel jacket. Recent inspections have shown that some tanks have significant defects in these thermal protection systems. This work was done to establish what levels of defect are acceptable from a safety standpoint.

The tests were conducted using 1890 l (500 US gallon) ASME code propane pressure vessels (commonly called tanks in the propane industry). The defects tested covered 8% and 15% of the tank surface. The tanks were 25% engulfed in a fire that simulated a hydrocarbon pool fire with an effective blackbody temperature of 870 °C.

The fire testing showed that even relatively small defects can result in tank rupture if the defect area is engulfed in a severe fire, and the defect area is not wetted by liquid from the inside. A wall failure prediction technique based on uniaxial high-temperature stress rupture test data has been developed and agrees well with the observed failure times.  相似文献   


4.
为评估LPG球罐发生BLEVE过程中超压与热耦合效应对化工企业抗爆控制室和避难所选址的影响,采用TNO多能法数学模型计算冲击波超压,采用多源数学模型计算火球热辐射。编写MATLAB计算程序,并应用ANSYS模拟二者破坏效应的耦合作用。LPG球罐发生BLEVE过程中,爆炸冲击波的传播速度、持续时间和火球的传播速度、持续时间不同,爆炸冲击波主要在燃料高速抛散的初期形成,之后基本与火球脱离。分别模拟计算冲击波超压和火球热辐射对抗爆控制室和避难所的影响,结果表明:抗爆控制室选址只需考虑爆炸冲击波的影响;避难所选址需要考虑冲击波超压和火球热辐射作用双重影响。在研究基础上提出,LPG球罐附近人员逃生的避难所应设置在球罐防火堤外紧邻防火堤处的地下,应具有抗震、防渗、防火、防中毒窒息等功能。人员应在BLEVE发生前进入避难所才能逃生。  相似文献   

5.
The article focuses on analyzing risks associated with the gas transfer operation in a liquified petroleum gas (LPG) bottling plant in India. The transfer operations involve transferring liquified gas from the transport tanker to the underground storage tank. Due to the rapid expansion of the cities, many LPG bottling plants in India got surrounded by residential areas and business centers. Moreover, to maintain the supply chain, the frequency of the transfer operations at the bottling plant also increased. In this scenario, an accidental release of LPG during the transfer operation may lead to various consequences such as a pool fire, a fireball, and even a catastrophic rupture of the tank with a successive explosion of its contents. In the study, the operations involved in bottling plants are classified into different hazard zones and analyzed. The probability of occurrence of events leading to an accident is modeled using modeling tools such as ALOHA and PHAST. The consequences of an accident following various events, such as jet fire, fireball, etc., are modeled, and the simulation results are compared. The thermal radiation has been estimated as 4–40 kW/m2, which could adversely affect the nearby population and could result in damaging plant machinery and equipment.  相似文献   

6.
大型LPG罐区火灾爆炸事故后果评估   总被引:2,自引:2,他引:2  
针对大型LPG(液化石油气)储罐区潜在的火灾爆炸危险性,建立了喷射火、火球、UVCE爆炸和BLEVE爆炸的数学伤害模型,对其发生火灾、爆炸后人员和建筑(设备)所受到的伤害和损伤进行了定量后果评估。  相似文献   

7.
针对重大危险源LPC罐区的火灾爆炸事故频发,首先采用数学泄漏模型分析油罐泄漏,然后应用池火、火球、喷射火火灾和UVCE及BLEVE爆炸事故的数学伤害模型分别分析几种重要的火灾和爆炸事故后果,并针对定量的事故后果分析对安全距离作出预测.  相似文献   

8.
The aging of many of the installations in the oil and gas industry may increase the likelihood of loss of containment of flammable substances, which could lead to major accidents. Flame temperatures in a typical hydrocarbon fire may reach 1100–1200 °C, which are associated with heat flux levels between 250 and 350 kW/m2. To limit or delay the escalation of an initial fire, passive fire protection (PFP) can be an effective barrier. Additionally, both equipment and piping may require thermal insulation for heat or cold conservation. Previous studies have investigated whether thermal insulation alone may protect the equipment for a required time period, e.g., until adequate depressurization is achieved. The present study entails the development of a numerical model for predicting the heat transport through a multi-layer wall of a distillation column exposed to fire. The outer surface is covered by stainless-steel weather protective cladding, followed by PFP, thermal insulation, and finally an inner column of carbon steel of variable thicknesses. The model for the breakdown of thermal insulation is based on observed dimensional changes and independent measurements of the thermal conductivity of the insulation after heat treatment. The calculated temperature profiles of thermally insulated carbon steel during fire exposure are compared to fire test results for carbon steel with thicknesses of 16, 12, 6 and 3 mm. The model's predictions agree reasonably well with the experiments. The degradation of the thermal insulation at temperatures above 1100 °C limits its applicability as fire protection, especially for low carbon-steel thickness. However, the model predicts that adding a 10-mm layer of more heat-resistant insulation (PFP) inside the fire-exposed cladding may considerably extend the time to breakdown of the thermal insulation.  相似文献   

9.
Fire protection of pressure vessels for transport and storage of dangerous goods is an active topic of research around the world. In many cases, organizations are conducting theoretical analysis followed by fire testing of thermal protection systems to determine how long they delay thermally induced failure, or if they eliminate failure. In most recent cases the organizations chose to do small scale fire testing because of the obvious cost savings.The question then is – are small scale experiments representative of highway tank truck and rail tank car scales? This paper discusses the scale issues involved. It goes on to show how identical fire heating conditions can give dramatically different failure times and modes of failure for small and large scale tanks if the conditions are not truly similar.  相似文献   

10.
This paper describes an experimental study of 2300 L pressure vessels exposed to remote fire heating by a natural gas fuelled wall fire simulator. The tanks were filled to 15% capacity with commercial liquid propane. The flame intensity and distance were varied to study the effect of different heating levels on the tank and its lading.The fire simulator is first characterized with tests including fire thermocouples, radiative flux meters and thermal imaging. With the appropriate positioning of a target tank it is possible to get very realistic fire heat fluxes at the tank surface.Three tests were conducted with the 2300 L tanks filled to 15% capacity with propane. The tanks were positioned at three different distances from the wall fire resulting in measured average peak heat flux at the tank surfaces ranging between 24 and 43 kW m?2. The data shows rapid rise in vapour space wall temperatures, significant temperature stratification in the vapour space, and moderate rate of pressure rise. These results provide excellent data for the validation of computer models used to predict the response of pressure vessels exposed to moderate heating from a remote fire.  相似文献   

11.
This paper presents an analysis and simulation of an accident involving a liquefied petroleum gas (LPG) truck tanker in Kannur, Kerala, India. During the accident, a truck tanker hit a divider and overturned. A crack in the bottom pipe caused leakage of LPG for about 20 min forming a large vapor cloud, which got ignited, creating a fireball and a boiling liquid expanding vapor explosion (BLEVE) situation in the LPG tank with subsequent fire and explosion. Many fatalities and injuries were reported along with burning of trees, houses, shops, vehicles, etc. In the present study, ALOHA (Area Locations of Hazardous Atmospheres) and PHAST (Process Hazard Analysis Software Tool) software have been used to model and simulate the accident scenario. Modeling and simulation results of the fireball, jet flame radiation and explosion overpressure agree well with the actual loss reported from the site. The effects of the fireball scenario were more significant in comparison to that of the jet fire scenario.  相似文献   

12.
为研究火灾中球罐应力场分布情况,找到球罐失效破裂条件,以液化石油气为研究对象,基于球罐稳态热响应,通过ANSYS热-结构耦合有限元分析法进行研究。结果表明:充装率85%的液化石油气球罐最高温度部位出现在气相区,约619.66 ℃;最大应力值出现在气液交界处,约615.18 MPa;得到球罐破裂失效时温度值和应力值,并设置2次预警值。研究结果可为液化石油气储罐失效预警提供参考和判定依据。  相似文献   

13.
事故树分析法在LPG储罐火灾爆炸事故中的应用   总被引:1,自引:0,他引:1  
LPG(液化石油气)属于危险化学品之一,LPG储罐发生火灾爆炸的机率大,造成的损失比较严重,故对其火灾爆炸事故进行研究具有重要意义。LPG储罐爆炸根据其发生机理分为化学爆炸(燃爆)和物理爆炸两种模式。本文通过对LPG储罐燃爆﹑物理爆炸两类事故进行系统分析,建立了以LPG储罐燃爆、物理爆炸为顶事件的事故树。通过对其事故树的定性分析,得到了影响顶事件的各个最小割(径)集。通过计算底事件的结构重要度,确定了影响LPG储罐火灾爆炸事故的主要因素,并提出了相应的改进措施,进而提高LPG储罐的安全性和运行可靠性。  相似文献   

14.
After the 2011 Tohoku earthquakes, several chemical and oil complexes on the Pacific Ocean shoreline of northeast Japan experienced massive losses. In Chiba, a refinery operated by Cosmo Oil lost 17 LPG storage vessels which were either heavily damaged or totally destroyed by fires and explosions in the refinery. These large vessels ranged in size from 1000 to 5000 m3. The estimated volume of LPG at the time of the incident was between 400 and 5000 m3 for each vessel. Five boiling liquid expanding vapor explosions (BLEVEs) of LPG occurred, resulting in huge fire balls measuring about 500 m in diameter.A BLEVE is defined as the explosive release of expanding vapor and boiling liquid when a container holding a pressure-liquefied gas fails catastrophically. It is thus important to estimate the physical properties of superheated liquids: the thermodynamic and transport properties, the intrinsic limits to superheating and depressurization, and the nature of thermodynamic paths. Also it is hoped to provide better understanding of the vessels designed, manufactured, installed, and operated to reduce or eliminate the probability that a sequence of events will result in BLEVE or loss of primary containment. Knowledge of these matters is still incomplete. The objective of this research is to estimate the significant BLEVE phenomenon in very large scale spherical vessels based on published information in Japan. There are some models predicting BLEVEs. However, it is essential to know if this is true for very large scales such as spheres since validation is usually rare to provide confidence in estimating the superheated liquids behaviors. To this end, comparing with the information on this event, the conditions in the five LPG vessels at the time of the BLEVE were determined in terms of: duration of vessel failure (time to BLEVE); mass fraction in the vessel with time; temperature distribution in the liquid and vapor region and pressure within the vessel (e.g. initial pressure and internal high-speed transient pressure during failure), by means of a computer program AFFTAC Analysis of Fire Effects on Tank Cars, which solves heat conduction, stress and a failure model of the tank, a thermodynamic model of its fluid contents, and a flow model for the lading flowing through the safety relief device. Subsequently, the consequences from the sphere BLEVE, such as the expected fireball diameter and duration and the expected blast overpressure produced by the BLEVE failures, are also subjects of active research. Here the blast using the methods of PHAST and SFPE Handbook of Fire Protection Engineering was calculated.Results suggest that methodologies here used gave reasonable estimations for such real and huge BLEVEs in a validated way, which may provide valuable guidance for risk mitigation strategy with regard to LPG facility in design, emergency planning, resiliency, operations, and risk management.  相似文献   

15.
When a chemical tank fire happens in a storage area, it is very important to protect adjacent tanks so as to decrease fire accident losses. In this paper, a new thermal protection method was put forward based on a PPH (potassium polyacrylate & hectorite) thermal insulation composite material spraying on an adjacent tank under fire. Firstly, the PPH material was prepared successfully by a polymerization reaction of potassium acrylate, hectorite, NaHSO3 and (NH4)2S2O8. Secondly, thermal insulation performance of the PPH material was characterized by heat transfer process at high incident heat flux using cone calorimeter. The results show that thermal insulation performance of the PPH material is affected by a content change of (NH4)2S2O8, NaHSO3 and hectorite in formulations. The content of (NH4)2S2O8 0.14 wt%, NaHSO3 1.38 wt% and hectorite 1.4 wt% was an optimum formulation ratio to obtain best thermal insulation performance. Finally, possible thermal insulation mechanisms of the PPH material were presented using SEM, TG and TG-IR techniques. One of the thermal insulation mechanisms is the incident heat flux absorbed by water evaporation from the PPH material. Another is the thermal protection of the char formed from the PPH material at high incident thermal radiation, which can prevent heat and mass transfer.  相似文献   

16.
Many railway tank-cars carrying hazardous materials are thermally protected from fire impingement by thermal insulation and a steel jacket applied to the outside of the tank-car shell. Over time, it is possible that the thermal insulation will sag, rip, degrade, or be crushed under the steel jacket. A thermographic technique to determine whether or not a tank has insulation deficiencies has been developed, but it is necessary to determine which thermal deficiencies do not affect a tank’s survivability in a fire and which thermal deficiencies must be repaired. In order to develop a guideline in assessing thermal defects, a thermal model and experimental data would be beneficial.A series of fire tests were performed on a quarter-section tank-car mock-up to assist in developing a guideline and to provide validation data for a thermal model. Twelve fire tests, with constant, credible, simulated pool fire conditions, were performed on the tank-car mock-up with various insulation deficiencies. An infrared thermal imaging camera was used to measure the tank wall temperature. The thermal images were useful in determining the temperature profiles across the defects at different times and the transient temperature behaviour at different locations.It was seen that the properly installed thermal protection system significantly reduced the heat transfer from the fire to the tank wall. It was also seen that the steel jacket alone (i.e. 100% defect) acted as a radiation shield and provided a significant level of protection. With small defects, it was observed that the surrounding protected material provided a cooling effect by thermal conduction. A square defect greater than about 40 cm on each side should be considered significant, because unlike smaller defects, there is little benefit from the surrounding material as far as the peak defect temperature is concerned.  相似文献   

17.
The BLEVE (boiling liquid expanding vapor explosion) effect that involves the formation of a fireball occurs at the engulfment by fire of a tank with a highly flammable liquid or a liquid gas. Heating of the tank causes elevation of the liquid phase temperature and pressure inside the tank. A partial rupture of the dry tank walls is possible, with the formation of a rarefaction wave propagating into the liquid phase. An evaporation wave moves after the rarefaction wave and cause a rapid increase of pressure, exceeding the initial pressure before depressurization. Rapid violent destruction of the tank occurs. The mechanism of a BLEVE initiation is considered using Van der Waals isotherms. The following criterion for the possibility of a BLEVE was formulated. If the final state is located on an unstable part of the Van der Waals isotherm, a BLEVE takes place. Limiting values of the temperatures for overheating of certain highly flammable liquids and liquid gases (propane, n-butane, n-pentane, isopentane) were calculated using the proposed method, and were found to be in good agreement with experimental data available in the literature.  相似文献   

18.
The measured blast overpressures from recent tests involving boiling liquid expanding vapour explosions (BLEVE) has been studied. The blast data came from tests where 0.4 and 2 m3 ASME code propane tanks were exposed to torch and pool fires. In total almost 60 tanks were tested, and of these nearly 20 resulted in catastrophic failures and BLEVEs. Both single and two-step BLEVEs were observed in these tests. This paper presents an analysis of the blast overpressures created by these BLEVEs. In addition, the blast overpressures from a recent full scale fire test of a rail tank car is included in the analysis.The results suggest that the liquid energy content did not contribute to the shock overpressures in the near or far field. The liquid flashing and expansion does produce a local overpressure by dynamic pressure effects but it does not appear to produce a shock wave. The shock overpressures could be estimated from the vapour energy alone for all the tests considered. This was true for liquid temperatures at failure that were below, at and above the atmospheric superheat limit for propane. Data suggests that the two step type BLEVE produces the strongest overpressure. The authors give their ideas for this observation.The results shown here add some limited evidence to support previous researchers claims that the liquid flashing process is too slow to generate a shock. It suggests that liquid temperatures at or above the Tsl do not change this. The expansion of the flashing liquid contributes to other hazards such as projectiles, and close in dynamic pressure effects. Of course BLEVE releases in enclosed spaces such as tunnels or buildings have different hazards.  相似文献   

19.
The road accident of a tanker transporting liquefied natural gas (LNG) originated a fire and, finally, the BLEVE of the tank. This accident has been analyzed, both from the point of view of the emergency management and the explosion and fireball effects. The accidental sequence is described: fire, LNG release, further safety valves release, flames impingement on vessel unprotected wall, vessel failure mode, explosion and fireball. According to the effects and consequences observed, the thermal radiation and overpressure are estimated; a mathematical model is applied to calculate the probable mass contained in the vessel at the moment of the explosion. The peak overpressure predicted from two models is compared with the values inferred from the accident observed data. The emergency management is commented.  相似文献   

20.
分析了密封圈火灾过程及特点,建立了压缩空气泡沫灭火试验装置,参照10×10~4m~3浮顶储罐建立了20 m长的密封圈试验装置,以汽油为介质开展了多次泡沫灭火试验。试验结果表明:该压缩空气泡沫灭火试验装置可在30 s内完成灭火,泡沫混合液供给强度约14~19 L/(min·m~2),具有在大型浮顶储罐上应用的可能性。针对单台10×10~4m~3浮顶储罐浮盘密封圈灭火提出了工程应用方案,该储罐共需泡沫液量1200 L,分为4套压缩空气泡沫灭火装置均匀分布在浮盘边缘,浮盘密封圈火灾报警系统与该泡沫灭火装置联锁启动自动灭火,各套灭火装置的持续喷射时间约1 min。  相似文献   